Heating Circuit 1, 2 And 3 - Viessmann VITODENS 200-W Service Instructions Manual

Table of Contents

Advertisement

Coding 2

Heating Circuit 1, 2 and 3

Coding in the factory setting
A4:0
A5:5
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Coding in the factory setting
A6:36
A7:0
62
(continued)
With frost protection
With heating circuit pump logic
function (economy mode):
Heating circuit pump "OFF"
when the outside temperature
(AT) is 1 K higher than the set
room temperature (RTset) AT >
RTset + 1 K
With heating circuit pump logic function: Heating circuit pump "OFF"
AT > RTset + 5 K
AT > RTset + 4 K
AT > RTset + 3 K
AT > RTset + 2 K
AT > RTset + 1 K
AT > RTset
AT > RTset - 1 K
AT > RTset - 9 K
Extended economy function
disabled
Without mixing valve economy
function
Vitodens 200-W B2HA 19, 28, 35 Service
Possible change
A4:1
No frost protection; this setting is
only possible if code "A3:-9" has
been selected.
Note: "Important" also coding
A5:0
Without heating circuit pump logic
function.
A5:1
With heating circuit pump logic
to
function: Heating circuit pump
A5:15
"OFF"; see following table.
Possible change
A6:5
Extended economy function
to
enabled, i.e. the burner and heating
A6:35
circuit pump will stop and the
mixing valve close at a variable
value, adjustable between 41 and
95° F (5 and 35° C) plus 1.8° F
(1° C). The base value
is the adjusted outside temperature.
This value is based on the actual
outside temperature and a time
constant, which takes the cooling
down of an average building into
consideration.
A7:1
With mixing valve economy
function (extended heating circuit
pump logic):
Heating circuit pump also "OFF":
- If the mixing valve has been
attempting to close for longer
than 20 minutes.
- Heating circuit pump "ON":
If the mixing valve changes to
control function.
- If there is a risk of frost.
address "A3".