Section 3-3-3: Heat Shields - Montigo PL42DF Installation & Maintenance Manual

Pl series
Hide thumbs Also See for PL42DF:
Table of Contents

Advertisement

PL42DF* Indoor Gas Fireplace

Section 3-3-3: Heat Shields

Installing a Wall Mounted RHS8 Heat shield
The RHS8 Heat shield CANNOT be used when the Termination is
WITHIN (36" Min. horizontal and 46" Min. vertical) from the fireplace,
or directly off the rear of the fireplace, as shown figure 16a. The
RHS101 Heat Shield (Figure 17 and 17a) MUST be used within the
noted dimensions.
To install the RHS8, frame an opening in combustible construction,
Figure 16 below. Slide the Heat shield in place over the vent pipe
which attaches to the fireplace. After the fireplace and vent pipe has
been installed, clearances should match the dimensions in Figure 16.
1" Min.
Figure 16.
RHS8 Installation. (Install by sliding over vent pipe where it
passes through the combustible construction).
36" Min
60" Min.
Figure 16a.
RHS8 Installation. (Minimum requirements).
Note: Images are shown without screens for clarity purposes.
However, your fireplace should not be operated without proper
installation of screens.
Page 18
Installation
1" Min. Both sides Typical
RHS8 Heat Shield
Combustible Framing
RHS8 Heat
Shield
PTO Termination
Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used where the RHS8 Termination
(Figure 16 and 16a) CANNOT be used. Use the RHS101 where any
of the dimensions are within the parameters shown, figure 16a.
To install the RHS101, Slide the Inner Section over the vent pipe
that will connect to the fireplace. Then fasten the vent pipe to the
back of the fireplace with a minimum of three sheet metal screws.
From the outside slide the RHS101 outer section on see Figure 17.
To complete the installation fasten the Heat Shield Outer Section
& Termination frame to the structure Figure 17a.
RHS101 Heat Shield
Outer Section
Termination
Figure 17. RHS101 Installation. (Install by sliding Outer Section over vent
pipe where it passes through the combustible construction.
RHS101 Heat Shield
Outer Section
Termination
Figure 17a. RHS101 Heat Shield after sliding the outer section in place.
3/8" Min.
Figure 17b.
RHS101 Installation.
Drywall / sheetrock
RHS101 Heat Shield, inner Section
Vent pipe, from fireplace
Combustible
framing
Drywall / sheetrock
RHS101 Heat Shield, inner Section
3/8" Min. Both sides Typical
Inner Shield 9 3/8"
Outer Shield 10 1/4"
Combustible Framing
XG0217 - 160215.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents