Program Dry Operation - Daikin 2MKS40G2V1B Service Manual

Inverter multi for 2 rooms g-series
Hide thumbs Also See for 2MKS40G2V1B:
Table of Contents

Advertisement

Function of Indoor Unit (RA Models)
COMFORT
Wall Mounted Type
AIRFLOW
Operation
1.6

Program Dry Operation

Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
Detail
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in the dry mode with an appropriate capacity for each zone to
maintain the temperature and humidity at a comfortable level.
temperature at start-up
59
The fan speed is controlled automatically within the following steps.
Cooling: L tap – MH tap (same as AUTOMATIC)
Heating: ML tap – M tap ~ MH tap (depending on the model)
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Room thermistor
Target temperature
24°C or more
Room thermistor
temperature at start-up
23.5°C
18°C
17.5°C
Zone C = Thermostat ON
Zone B
Y
Zone A = Thermostat OFF
Thermostat OFF point
X
X
X
18°C
X
Zone B
SiBE12-816_D
Thermostat ON point
Y
Z
X
0.5°C
or
2.5°C
Y + 0.5°C (zone B)
continues for 10 min.
X
0.5°C
or
2.0°C
Y + 0.5°C (zone B)
continues for 10 min.
X
0.5°C = 17.5°C
or
2.0°C
Y + 0.5°C (zone B)
continues for 10 min.
X
Z
+0.5ºC
(R11581)
Function and Control