Check
8.7
Inverter Unit Refrigerant System Check
Check No.14
265
Refrigerant system check
Is the
discharge pipe
thermistor disconnected
from the holder?
NO
Check for refrigerant leakage.
See the section on refrigerant
shortage detection.
YES
SiBE12-816_D
Place the thermistor.
Replace the refrigerant.
(R8380)
Service Diagnosis