Forced Cooling Operation

2. Forced Cooling Operation

Conditions
Start
Operating room
Command frequency
End
Others
ex. Wall mounted type FTXS Series
299
Item
The forced cooling operation is allowed when both the following conditions
are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
All rooms
40 class: 70 Hz
50 class: 47 Hz
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor
unit again.
The protection functions are prior to all others in the forced cooling
operation.
Forced Cooling
ON/OFF button (SW1)
(R14226)
Trial Operation and Field Settings
SiBE12-816_D