To incorporate the IBF into the room EPO, a cable connection must be made to connect to the back of the
system UEPO panel. The following diagrams illustrate how this connection is made.
The preceding figure illustrates the back of the machine UEPO panel with the room EPO cable plugging
into the machine. After the switch actuator is moved to make the cable connection possible, the room EPO
cable must be installed for the machine to power on.
In the following figure, an AMP connector 770019-1 is needed to connect to the system UEPO panel. For
room EPO cables using wire sizes #20 AWG to #24 AWG, use AMP pins part number 770010-4.
4
AMP Connector
3
1
2
Part Number - 770019-1
Contact Number
2 Pole Normally Closed Pushbutton

Step 8. Check the Outlets and the Power Source

CAUTION:
Do not touch the receptacle or the receptacle faceplate with anything other than your test probes
before you have met the requirements in below.
Do the following to ensure that the customer has provided the correct power to the system:
__ 1. This system is equipped to use 200-240 V / 380-415 V / 480 V ac, three-phase. Check that the
correct power source is available.
Chapter 2. Installing the pSeries 670