Upright Installations; Horizontal Installations; Startup Procedure & Adjustment; Heat Anticipator Setting - Goodman AKSS9/GKS9 Installation Instructions Manual

Gas-fired warm air furnace
Table of Contents

Advertisement

*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
U
I
PRIGHT
NSTALLATIONS
Depending on the installation and/or customer preference, differ-
ing filter arrangements can be applied. Filters can be installed in
the central return register or a side panel external filter rack kit
(upflows). As an alternative a media air filter or electronic air cleaner
can be used as the requested filter.
The following figure shows possible filter locations.
CENTRAL
RETURN
GRILLE
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Possible Upright Upflow
Filter Locations
H
I
ORIZONTAL
NSTALLATIONS
Filters must be installed in either the central return register or in the
return air duct work.
XIV. STARTUP PROCEDURE & ADJUSTMENT
Furnace must have a 115 VAC power supply properly connected
and grounded. Proper polarity must be maintained for correct op-
eration. In addition to the following start-up and adjustment items,
refer to further information in Section XVI, Operational Checks.
H
A
S
EAT
NTICIPATOR
ETTING
The heat anticipator in the room thermostat must be correctly ad-
justed to obtain the proper number of cycles per hour and to pre-
vent "overshooting" of the setting. Set the heat anticipator setting to
0.7 amps. Follow the thermostat manufacturer's instructions on
how to adjust the heat anticipator setting.
D
T
P
RAIN
RAP
RIMING
The drain trap must be primed prior to furnace startup. To prime, fill
the drain trap with water. This ensures proper furnace drainage
upon startup and prohibits the possibility of flue gases escaping
through the drain system.
F
URNACE OPERATION
Purge gas lines of air prior to startup. Be sure not purge lines into
an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
method. Verify that all required kits (propane gas, high altitude,
etc.) have been appropriately installed.
AIR FLOW
F
S
URNACE
TARTUP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF position.
6. Wait five minutes then smell for gas. Be sure to check near the
floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the
instructions on page 4 of this manual. If you do not smell
gas after five minutes, move the furnace gas valve manual
control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
F
S
URNACE
HUTDOWN
1. Set the thermostat to the lowest setting.
The integrated control will close the gas valve and extinguish
flame. Following a 15 second delay, the induced draft blower
will be de-energized. After a 150-second delay period (fixed),
the circulator blower will be de-energized.
2. Remove the burner compartment door and move the furnace
gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
G
S
P
AS
UPPLY
RESSURE
T
 
 
 
O
PREVENT
UNRELIABLE
OPERATION
 
 
 
INLET
GAS
SUPPLY
PRESSURE
 
 
 
 
RATING
PLATE
WITH
ALL
OTHER
.
OPERATING
HIGH VOLTAGE !
D
 
 
 
ISCONNECT
ALL
POWER
BEFORE
 
 
. M
INSTALLING
THIS
UNIT
ULTIPLE
 
. F
 
 
BE
PRESENT
AILURE
TO
DO
 
DAMAGE
PERSONAL
INJURY
The line pressure supplied to the gas valve must be within the
range specified below. The supply pressure can be measured at
the gas valve inlet pressure tap or at a hose fitting installed in the
gas piping drip leg. The supply pressure must be measured with
the unit OFF. To measure inlet pressure, use the following proce-
dure.
28
M
EASUREMENT
CAUTION
 
 
 
OR
EQUIPMENT
DAMAGE
 
 
 
 
 
 
MUST
BE
AS
SPECIFIED
ON
THE
 
 
 
 
HOUSEHOLD
GAS
FIRED
APPLIANCES
WARNING
 
 
 
SERVICING
OR
 
 
 
 
POWER
SOURCES
MAY
 
 
 
 
 
SO
MAY
CAUSE
PROPERTY
 
 
.
OR
DEATH
 
THE
 
 
UNIT
 