TROUBLESHOOTING

For ease of service, the systems are equipped with diagnostic code
display LEDs on both the indoor and outdoor units. The outdoor
diagnostic display consists of two LEDs (Red and Green) on the
outdoor unit board and is limited to a few errors. The indoor
diagnostic display is a combination of flashing LEDs on the
INDOOR UNIT DIAGNOSTIC GUIDES
Operation Lamp
Timer Lamp
X
1 time
2 times
X
4 times
X
5 times
X
6 times
X
7 times
X
8 times
X
1 time
O
2 times
O
3 times
O
4 times
O
5 times
O
6 times
O
7 times
O
8 times
O
9 times
O
10 times
O
1 time
2 times
3 times
4 times
5 times
6 times
7 times
8 times
(flash)
O (light) X (off)
For additional diagnostic information, refer to the Service Manual.
OUTDOOR UNIT DIAGNOSTIC GUIDES
LED2
LED1
(Green)
(Red)
O
X
X
O
O
X
O
O
X
O
☆ = Flashing, X = Off
For additional diagnostic information, refer to the Service Manual
Table 7—Indoor Unit Diagnostic Guides
Display
LED Status
E0
Indoor unit EEPROM error
E1
Communication malfunction between indoor and outdoor units
E3
Indoor fan speed has been out of control
E4
Indoor room temperature sensor T1 open circuit or short circuit
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
EC
Refrigerant leakage detection
EE
Water--- level alarm malfunction
F0
Current overload protection
F1
Open circuit or short circuit of outdoor ambient temperature sensor T4
F2
Open circuit or short circuit of condenser coil temperature sensor T3
F3
Open circuit or short circuit of Compressor discharge temperature sensor T5
F4
Outdoor unit EEPROM error
F5
Outdoor fan speed has been out of control
F6
T2B sensor error
F7
Lifting --- panel communication error
F8
Lifting --- panel malfunction
F9
Lifting --- panel is not closed
P0
IPM malfunction
P1
Over voltage or over low voltage protection
P2
High temperature protection of compressor top
P3
Outdoor low temperature protection
P4
Inverter compressor drive error
P5
Mode conflict
P6
Compressor low--- pressure protection
P7
Outdoor IGBT temperature sensor error
Table 8—Outdoor Unit Diagnostic Guides
Indoor Unit display
Failure Mode
Standby, normal
Operation, normal
E5
Compressor drive board EEPROM error
P0
IPM malfunction or IGBT over---strong current protection
P1
Over voltage or too low voltage protection
P4
Inverter compressor drive error
P4
Inverter compressor drive error
P4
Communication malfunction between main control board and driver board
display panel or the front of the unit. If possible, always check the
diagnostic codes displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are
listed in the tables below.