Troubleshooting Guide - Cornelius MILLENNIUM MJ41-6PB Installation & Service Manual

Table of Contents

Advertisement

TROUBLESHOOTING GUIDE

Problem
UNIT IS DISPENSING
CONCENTRATE ONLY
REFRIGERATION SYSTEM
HAS BEEN RUNNING FOR
EXTENDED PERIOD
WITHOUT SHUTTING OFF
FROZEN WATER COIL
Probable Cause
Blocked condenser fins.
Ambient air over 100°F 38°C.
Defective overload.
Defective compressor.
Insufficient water level in the
water bath.
Agitator motor not operating.
Improperly located ice bank
control sensor.
Compressor not cycling off.
17
Remedy
DISPENSER. This will block the
airflow over heating the compressor
and causing it to trip the overload.
Remove the rear bonnet and check
the condenser fins. If unit is run in a
dusty environment, condenser fins
can become clogged, stopping the air
flow.
Brush out and clean with vacuum.
If the dispenser is working in an
environment
over
100
ambient or is drawing in discharged
air, during a heavy period, the unit
may trip the overload.
Overload works on shell temperature
and amperage draw and can be
defective. Replace as needed.
Refrigeration technician will verify if
the compressor is defective and needs
to be replaced.
See
the Start-up and Operation
Section of this manual. Be sure the
water bath is filled to fill line.
Check the agitator motor located on
the refrigeration deck. Be sure it is
plugged in and
receiving power.
Check that the impeller is not
obstructed. Replace if needed.
Melt the ice bank and check the
location of the sensing bulb. Be sure
it is all the way down to the bottom
of the tube.
Check the ice bank control. Be sure
that the control has not overheated
and fused the contacts together.
Replace as required.
degrees