6. TROUBLE SHOOTING
Outdoor coil anti-overload
protection with cooling
IPM module protection
PFC protection
Compressor pre heating
process
Chip in outdoor board in
trouble
AC voltage higher or lower
protection
DC compressor start failure
a.the refrigerant is too much;
b.the outdoor fan motor is failure;
c.the outdoor fan is broken;
d.the condensor is dirty;
e.the air inlet and air outlet of the
indoor unit and the outdoor unit is
not normally
a.The IPM board is failure;
b.The outdoor fan is broken;
c.The outdoor fan motor is failure;
d.The outdoor fan has been
blocked ;
e.The condenser is dirty;
f.The outdoor unit has been
installed without standard.
a.the PFC is failure;
b.the outdoor drive board is failure
it is normal mode in cold weather
a. Using the wrong drive board;
b. Using the wrong compressor.
a.the supply voltage is higher or
lower than normal;
b.the inner supply voltage of the
unit is higher or lower than normal
a.the outdoor drive board is failure;
b.the compressor is failure