Troubleshooting by Indication on the Remote Controller
Troubleshooting
Check No.2
150
Caution
Is the
stop valve
open?
1 Mount a pressure gauge on the low-pressure service port.
2 Connect the Service Tool
3 Reset the operation using the remote control, and then restart
the operation.
Are the
characteristics of
the low pressu re sensor
normal? ( S ee
Is the
pressu re
detected with the PC
board normal?
(See *2.)
· The low pressure sensor is normal, and the pressure detected
with the PC board is also normal.
· The low pressure has really become low.
Refer to "remove the causes by which the low
CHECK 2
pressu re has become l o w".
*1: Make a comparison between the voltage of the p ressu re sensor (*4) and that read by the
pressu re gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector, and
and then convert it to pressure.)
*2: Make a comparison between the low pressu re value checked with the Ser vi c e Tool
and the voltage of the p ressu re sensor (see *1) .
*3: Make measu rement of voltage of the p ressu re sensor.
Micro controller
A/D input
Make measurement of DC voltage between these wires. (*4)
: ∗ Refer to information on page 207.
NO
YES
NO
*1.)
YES
NO
YES
+5V
Connector for low pressu re sensor
(Blue)
(4)
(3)
(2)
(1)
Open the stop valve.
Replace the low pressure sensor.
Replace the main PC board.
Red
Black
Low
pressure
White
sensor
Troubleshooting
ESIE09-08