Daikin ERSQ 011AAV1 Service Manual page 121

Table of Contents

Advertisement

ESIE09-08
b. "Setting mode 2"
Push and hold the MODE (BS1)
button for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET (BS2) button and set
to the setting condition you want.
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of "Setting
mode 2".
∗ If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
Test Operation
No.
Setting item
Refrigerant
recovery /
21
vacuuming mode
setting of R-410A
circuit
Automatic pump
61
down operation
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Remark: Pump down operation is ONLY ALLOWED when the refrigerant
charge is less than
(V2764)
Sets to refrigerant recovery or vacuuming mode.
An automatic pump down operation which will collect all
refrigerant from the field piping and indoor unit in the
outdoor unit.
4,5kg.
Field Setting
Description
109