Daikin ERSQ 011AAV1 Service Manual page 81

Table of Contents

Advertisement

ESIE09-08
Remote controller room temperature control
When the reheat temperature is reached, the further heat up till storage temperature of the
domestic hot water tank will be decided by the remote controller room thermostat in order to
prevent that the room temperature drops too much.
1. Reheat operation
Function
When requesting space heating and domestic water heating (reheat) at the same time. This
involves that the minimum reheat temperature is reached (setting [b-00]) during space
heating operation. The 3-way valve will switch over to the domestic hot water side. The
domestic water will be heated till maximum reheat temperature (setting [b-01]). The 3-way
valve will switch back to original position, then space heating will start again.
During the reheat operation, the system does not take care about the room temperature.
This means that during simultaneous demand, the reheat operation has priority over the
room temperature.
K
E
D
J
C
H
B
A
M
A
Operation
Space heating
Domestic water heating
B
Domestic hot water reheat thermo-on request
C
Domestic hot water tank temperature
D
Room temperature thermo-on request
E
Remote controller room temperature
F
Domestic hot water lower limit temperature
G
Domestic hot water upper limit temperature (maximum possible storage temperature)
[b-03]
H
Domestic hot water reheat minimum temperature [b-00]
J
Domestic hot water reheat maximum temperature [b-01]
K
Remote controller thermostat set point
M
Simultaneous demand
N
ONLY space heating request
ON
ON
OFF
OFF
+0.5°C
–0.5°C
–3.0°C
ON
OFF
G
75°C
F
35°C
ON
OFF
N
Outline of Control (Indoor Unit)
69