Troubleshooting by Indication on the Remote Controller
[CHECK 3] Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector on motor side disconnected, measure the resistance between
208
each pin, then make sure that the resistance is more than the value mentioned in the
following table.
1 White
2 Orange
3 Brown
GND
4 Blue
5
6
7 Red
Measurement point
Judgment
1 - 4
1MΩ or more
2 - 4
100kΩ or more
3 - 4
100Ω or more
4 - 7
100kΩ or more
ESIE09-08
Troubleshooting