Field Setting
The following settings are made by pushbutton switches on PC board.
There are the following three setting modes.
Initial status (when normal): Also indicates during "abnormal".
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Used to check the program made in Setting mode 2.
106
LED'S DURING initializing: first 12 minutes after power starting
H1P
LED indication
Wait until initializing period is over before pressing buttons.
Setting by pushbutton switches
H1P
LED indication
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure
H2P
H3P
H4P
c
H2P
H3P
BS1
BS2
BS3
BS4
MODE
SET
RETURN
TEST
(Normal)
Push the BS1(MODE button)
one time.
Setting mode 1
MODE
Off
H1P
H5P
H6P
H7P
H4P
H5P
H6P
(Factory setting = normal operation)
BS5
RESET
(V2760)
Monitor mode
MODE
H1P
Test Operation
ESIE09-08
H8P
c
H7P
Blinking
(V2761)