Output Terminal Panel Connections - MULTIQUIP Whisperwatt DCA150SSJU4F Operation And Parts Manual

60hz
Table of Contents

Advertisement

3Ø-480/277v uvWo terminal output voltages
1. Place the voltage selector switch in the 3Ø 480/277
position as shown in Figure 22.
Figure 22. Voltage Selector itch
3Ø-480/277V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 23.
Figure 23. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
alWaYs make sure that the connections to the UVWO
terminals are secure and tight. The possibility of arcing
exists, that could cause a fire.
dca150ssju4f 60 hz generator• operation manual — rev. #0 (11/0614) — page 27

OUtpUt terMiNaL paNeL CONNeCtiONs

1Ø-240/120v uvWo terminal output voltages
1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 24.
Figure 24. Voltage Selector itch
1Ø-240/120V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs
1Ø-240/120V Connection
3. Turn the voltage regulator knob (Figure 20) clockwise
to increase voltage output, turn counterclockwise
to decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.