Troubleshooting
Checking and acknowledging faults
Fault code
Const.
in the dis-
play
F4
X
F7
X
F8
X
F9
X
82
Weat-
System
h.
character-
comp.
istics
X
Burner in
fault state
X
Burner
blocked
X
Burner in
fault state
X
Burner in
fault state
(cont.)
Cause
No flame signal is
present
Differential pres-
sure sensor faulty
Fuel valve closes
too late
Fan speed too low
at burner start
Remedy
Check the
ionisation
electrode and
leads, mea-
sure the ioni-
sation cur-
rent, check
the gas pres-
sure, check
the gas com-
bination
valve, igni-
tion, ignition
module, igni-
tion electro-
des and the
condensate
drain.
Press E
Check the dif-
ferential pres-
sure sensor
and lead.
Check gas
combination
valve. Check
both control
paths.
Press E
Check the
fan, check the
fan cables
and supply,
check the fan
control.
Press E