Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
No display correction of
the actual room tem-
perature.
Mixer circuit
F1:0
Screed function inactive
(only for weather-com-
pensated control units)
60
Coding
Possible change
change
Address:
value
E2:99
display correction +4.9 K
F1:1
Screed drying function
to
adjustable in accordance
F1:5
with 5 optional tempera-
ture time profiles (see
page 106).
Note
Observe the screed dry-
ing supplier's instruc-
tions.
Observe DIN 4725-2 or
local regulations. The
report to be provided by
the heating contractor
must contain the follow-
ing heat-up details:
&
Heat-up data with
respective flow tem-
peratures
&
Max. flow temperature
achieved
&
Operating condition
and outside tempera-
ture during handover
The function continues
after power failure or
after the control unit has
been switched OFF. The
rw heating program
will be started after the
screed-drying function
has been completed, or if