4.1.4 Metering for the Domestic Renewable Heat Incentive - UK

Please take note of the following requirements if the installation is to be fitted with a meter;
Leave sufficient space for appropriate meters to be fitted in defined locations.
For Dimplex installations using 22mm pipe, please leave 440mm of straight pipework on the
meter inlet pipe and 175mm of straight pipework on the outlet pipe;
For installations using 28mm pipe, please leave 560mm of straight pipework on the meter inlet
pipe and 175mm of straight pipework on the outlet pipe.
Install low pressure-drop isolation valves to avoid the need to drain systems when fitting heat
meters. See the schematics (Appendices) for more information on valve locations.
Leave sufficient pipework accessible, i.e. not boxed in or under floor boards, to enable meters to
be fitted.
Guidelines for fitting an MCS approved meter can be found in the Domestic Renewable Heat
Incentive essential guide to metering, available on the Ofgem website: www.ofgem.gov.uk