611. Output 1 Type
880. Alarm Message Minimum Repeat Time
Enter how long the control center waits between alarm message announcements before
repeating the message even if the control center's proximity sensor detects motion.
Bosch Security Systems, Inc.
Disabled: Output is disabled.
Intrusion: Output turns on when intrusion alarm occurs. To turn off output, turn off
system, or wait until end of intrusion bell cut-off time.
Fire: Output turns on when a fire alarm occurs. To turn off output, turn off system if it is
already on, or wait until end of fire bell cut-off time.
Fire Latching: Output turns on when a fire alarm occurs. To turn off output, turn off
system if it is already on, or acknowledge alarm if system is off.
Intrusion and Fire: Output turns on when an intrusion or fire alarm occurs. To turn off
output, turn off system, or wait until end of bell cut-off time. Fire alarms take priority over
intrusion alarms.
Intrusion and Fire Latching: Output turns on when an intrusion or fire alarm occurs. To
turn off output, turn off system if it is already on, or acknowledge alarm if system is off.
Fire alarms take priority over intrusion alarms.
System Reset: Output is normally on. Output turns off for approximately 10 sec when
system is reset. Use this function to supply power to devices such as four-wire smoke
detectors that require power interruption to reset a latching alarm condition
System On: Output turns on when the system is turned on, and remains on until system
is turned off.
System Ready: Output turns on when the system is ready to turn on (no faulted points or
system troubles exist).
Key Fob On/Off: Output turns on or off when the user presses the key fob's
key.
Key Fob 2-sec Pulse: Output turns on for two seconds when the user presses the key
fob's
or
key.
User Controlled: Output turns on or off when a user or the installer uses the Operate
Outputs option from the phone menus.
Interior Intrusion and Fire: Output turns on when an interior intrusion or fire alarm
occurs. To turn off output, turn off system, or wait until end of bell cut-off time. Fire
alarms take priority over intrusion alarms.
System On (Unoccupied): Output turns on when the system is turned On (Unoccupied)
and there are no bypassed or force-armed points.
Intrusion and Fire:
Output turns on when any alarm (Intrusion or Fire) occurs. To turn off the output,
turn off the system, or wait until the end of the bell cut-off time.
When a fire alarm occurs, this output function provides only a steady output (no
Temporal Code 3 or Pulsed cadence).
Fire alarms take priority over Intrusion alarms.
System Reference Guide