102 en | Programming Details and Defaults
11

Programming Details and Defaults

This section defines the primary function of the major programming items.
This section also lists the programming defaults for the most frequently used country codes.
11.1

Programming Item Programming Details

102. Country Code
Select the appropriate code for country-specific operation.
107. Fire Bell Cut-off Time
Enter how long the fire alarm sounds at bell outputs and at the control center.
108. Intrusion Bell Cut-off Time
Enter how long the intrusion alarm sounds at bell outputs and at the control center.
110. Intrusion Abort Window
Enter how long the control panel waits to send an alarm report after an alarm occurs.
111. Fire Alarm Cancel Window
Enter how long a user has to cancel a fire alarm report after the system sends the report to
the central station. If a fire alarm is acknowledged during the cancel window, the system
sends a cancel report to the central station. An entry of 0 disables this feature.
112. Intrusion Cancel Window
Enter how long a user has to cancel an intrusion alarm report after the system sends the
report to the central station.
115. Chime Mode Operation after System Off
Determines Chime Mode operation after the system is turned off.
116. Automatic Test Report Frequency
Determines how often the control panel sends the automatic test report.
118. RPS Passcode
Enter the 6-digit passcode that allows access to the control panel from RPS.
124. Point Alarm Verification
Determines the level of alarm verification required by point before generating an intrusion
alarm condition.
125. Faulted Points Allowed Threshold
Determines the maximum number of faulted points that are disabled while the system is on.
126. Exit Delay
Enter how long the user has to exit the building before the system turns on.
127. Entry Delay
Enter how long the user has to enter the building and turn off the system before an alarm
condition occurs.
131. Swinger Bypass Count
Enter the number of alarm reports allowed from a point while the system is on before the
point is bypassed.
133. System On Order Options
Determines the order that system-on options are announced to the user.
134. Cross Zone Timer
Enter how long the system waits for at least two Cross Zone points to be faulted before the
control panel sends a Verified Alarm report to the central station.
F01U087835 | 02 | 2008.10
System Reference Guide
Easy Series