OPERATION
6. Press the RESET button:
• The RESET button should be flush with the base.
• If the RESET button is not flush with the TEST button, contact an
authorized Honda generator dealer.
7. Check the GFCI LED to see if it is correctly functioning.
• The LED is lit during normal operation.
• The LED is not lit during a GFCI test.
• The LED is not lit if the GFCI is faulty. Contact an authorized
Honda generator dealer.
When the RESET button extends or the GFCI LED is not lit during
operation.
• Unplug all appliances from the GFCI protected receptacle.
• Press the RESET button.
– If the GFCI cannot be reset, the GFCI is faulty. Contact an authorized
Honda generator dealer.
– If the RESET button extends, this usually indicates a faulty
power tool, appliance, or cord. If that occurs, perform operation
check steps 1 through 7 to verify that the GFCI is in proper
working order. If the GFCI tests correctly, then the fault is likely
to be in the power tool, appliance, or cord. Repair or replace the
faulty power tool, appliance, or cord before further use.