50 | Making the electrical connections
▶ Connect white plugs and insert grommet until stop.
Fig. 57 Cable connected (mains power supply)
▶ Mount junction box on the rail.
7.4

Connecting the LWCO device

NOTICE: System damage or malfunction!
▶ Ensure the air box remains air-tight when routing the
LWCO cable to the outside.
▶ Do not route the LWCO cable through the ignition
cable grommet as appliance malfunction may occur.
▶ Punch a hole (maximum diameter 3/16" (5 mm)) through the fan
cable grommet (steps 1 – 3) and run the LWCO cable through it.
Fig. 58 Punch a hole in fan cable grommet for LWCO cable
▶ Install a 24VAC 20VA transformer near the boiler.
▶ Follow LWCO manufacturer's instructions.
▶ Connect the lead labeled BOILER GROUND (green) to pin 2 (center,
 Fig. 56 [2]) of the white plug in the boiler junction box.
▶ Connect the leads labeled 24V HOT (red) and 24V COMMON (white)
to the external 24VAC transformer.
6 720 806 992 (2015/03)
6 720 641 933-39.1O
Ø ≤ 3/16"
(~ 5 mm)
1
2
3
6 720 641 933-87.1O
▶ Connect the leads labeled SWITCH CONTACT (yellow) to the TB1
temperature guard ( Fig 47, page 47) on the Heatronic.
1
Fig. 59 Wires of a LWCO device with LWCO adapter
[1]
LWCO device (Hydrolevel Safgard 1100)
[2]
BOILER GROUND (green)
[3]
SWITCH CONTACT (yellow)
[4]
SWITCH CONTACT (yellow)
[5]
24V HOT (red)
[6]
24V COMMON (white)
2
3
4
5
6
6 720 641 933-67.1O