Gas type conversion
DANGER: Personal injury and property damage
▶ This conversion shall only be performed by a trained and
certified installer in accordance with the manufacturer's
instructions and all applicable codes and requirements of the
authority having jurisdiction.
▶ If the information in these instructions is not followed exactly,
or the installation, adjustment, modification, operation or
maintenance is carried out by an unqualified person, a fire,
explosion or generation of large amounts of carbon monoxide
may result causing property damage, personal injury or loss of
life.
▶ Before carrying out electrical work: disconnect the
installation from the power supply at the emergency shutoff
switch or by disengaging the heating system circuit breaker.
Take measures to prevent accidental reconnection.
▶ The installer is responsible for the proper conversion of this
appliance.
▶ The conversion is not complete until the operation of the
converted appliance is checked as specified in these
instructions.
The gas-air ratio must always be set on the basis of a CO
maximum nominal output and minimum nominal output using an electronic flue
gas analyzer.
Adjustment to different flue systems using throttle discs or baffles is not necessary.
NG
Appliances are set at the factory to Wobbe index 1,333 BTU/ft
60 °F (15 °C), 30" Hg (1016 hPa) and 7.0" W.C. (17.4 mbar) gas supply
pressure and sealed.
Converting to a different gas type
DANGER: Explosion!
▶ Close the gas cock prior to working on the gas train.
▶ Check for gas leaks after carrying out work on the gas train.
A gas conversion kit is included in the scope of delivery.
▶ Fold the Heatronic down.
▶ Check the number on the code plug from the gas conversion kit:
NG Code plug
Appliance
Order number
ZBR16-3A
8 714 432 501 0
ZBR21-3A
8 714 432 528 0
ZBR28-3A
8 714 432 502 0
ZBR35-3A
8 714 432 503 0
ZBR42-3A
8 714 432 504 0
ZWB28-3A
8 714 432 520 0
ZWB35-3A
8 714 432 524 0
ZWB42-3A
8 714 432 500 0
▶ Replace the code plug in the Heatronic with the code plug from the gas
conversion kit.
Fig. 1
Replacing the code plug
Greenstar
▶ Affix the gas type label from the gas conversion kit to the appliance.
Fig. 2
▶ Always adjust the gas-air ratio (CO
Installation location higher than 2,000 feet (610 m) above sea level
Input and output rates are reduced at higher altitudes due to thin air with reduced
oxygen levels.
ZBR42-3A... and ZWB42-3A... appliances are derated at 3 % per 1000 feet
(305 m).
ZBR16-3A..., ZBR21-3A..., ZBR28-3A..., ZBR35-3A..., ZWB28-3A... and
ZWB35-3A appliances offer altitude adjustment which compensates for the effects
of thin air, and are therefore NOT derated up to 6000 feet (1829 m). Above
or O
reading taken at
2
2
6000 feet (1829 m) a rate of 3 % per 1000 feet (305 m) applies.
3
3
(49.6 MJ/m
) at
▶ Correction of the fan speed curve of the burner:
Setting the gas-air ratio (CO
▶ Switch the appliance OFF using the ON/OFF switch.
▶ Remove the cover ( "Installation and Service Instructions for Contractors").
▶ Switch the appliance ON using the ON/OFF switch.
▶ Open one of the flue gas test ports.
LPG Code plug
Order number
8 714 432 506 0
8 714 432 529 0
8 714 432 507 0
8 714 432 508 0
Fig. 3
8 714 432 509 0
▶ Insert the flue gas probe approx. 2-3/4 inches (70 mm) into the test port and
8 714 432 521 0
8 714 432 525 0
▶ Press and hold the emissions test button
8 714 432 505 0
▶ Briefly press the emissions test button
▶ Measure the CO
6 720 641 933-57.1O
Affixing the gas type label
2
after converting to a different gas type and measure the CO content of the flue
gas ( "Installation and Service Instructions for Contractors").
The Bosch Greenstar boiler is factory set for installation below
2000 feet (610 m) above sea level.
Use service function 0.d to adjust the elevation setting ( "Installation and
Service Instructions for Contractors").
or O
)
2
2
Open one of the flue gas test ports
seal around it.
The display shows the supply temperature alternating with
output in heating mode.
The display shows the supply temperature in alternation with
nominal output.
or O
level and the CO content of the flue gas ( "Installation
2
2
and Service Instructions for Contractors").
6 720 641 933-58.2O
,  Section "Setting the gas-air ratio")
or O
2
6 720 641 933-79.1O
until it lights up.
= maximum set
.
= maximum
6 720 646 558 (2013/07)
| 1

Advertisement

loading

Summary of Contents for Bosch ZBR16-3A

  • Page 1 The Bosch Greenstar boiler is factory set for installation below Adjustment to different flue systems using throttle discs or baffles is not necessary. 2000 feet (610 m) above sea level.
  • Page 2 ▶ On the the gas throttle break the seal at the slot and remove the cap. ▶ Remove flue gas probe and close the flue gas test port properly. 6 720 641 933-80.1O Fig. 7 Close flue gas test ports 6 7 2 0 6 1 2 6 5 9 - 3 7 .
  • Page 3 (15 °C), 30" Hg (1016 hPa) et 7,0" W.C. (17,4 mbar), puis scellés. pour 1 000 pieds (305 m) apparaît. Conversion à une autre catégorie de gaz Les types d'appareils ZBR16-3A..., ZBR21-3A..., ZBR28-3A..., ZBR35-3A..., ZWB28-3A... et ZWB35-3A disposent d'un adaptateur, dispositif qui compense les DANGER: explosion ! effets d'un air raréfié, si bien que la puissance n'est AUCUNEMENT entravée à...
  • Page 4 ▶ Insérer la sonde des fumées d’env. 2-3/4 pouces (70 mm) dans la buse de ▶ Appuyer sur la touche ramonage autant de fois que nécessaire pour qu’elle mesure des fumées et étanchéifier le point de mesure. s’éteigne. L’afficheur indique à nouveau la température de départ chauffage. ▶...

This manual is also suitable for:

Zbr21-3aZbr28-3aZbr35-3aZbr42-3aZwb28-3aZwb35-3a ... Show all