FOR YOUR SAFETY
Do not store or use gasoline or any other flammable
vapors or liquids in the vicinity of this or any other
appliance.
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
Do not place clothing or other flammable materials on
or near the appliance.
NEVER leave children unattended when a fire is
burning in the fireplace.
WARNING: IMPROPER INSTALLATION, ADJUST-
MENT, ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY, PROPERTY DAMAGE, OR
LOSS OF LIFE. REFER TO THIS MANUAL FOR
ASSISTANCE OR ADDITIONAL INFORMATION.
CONSULT A QUALIFIED INSTALLER OR LOCAL
DISTRIBUTOR.
CHECK
HUD
INSTALLING THIS FIREPLACE.

INTRODUCTION

Model 36LM/RM is specifically designed for use in
manufactured mobile homes. This fireplace includes a manual
control fan system, combustion air kit and bi-fold doors with a
brushed brass finish.
BEFORE YOU BEGIN
♦ Before beginning the installation of the fireplace, read
these instructions through, completely.
♦ These DESA components and fireplace are safe when
installed according to this Installation Manual. Unless you
use DESA components, which has been designed and
tested for the fireplace system, you may cause a fire
hazard.
♦ The DESA warranty will be voided by and DESA
disclaims any responsibility for the following actions:
a) Modification of the fireplace, components, doors, blower,
fans, air inlet system and damper control.
b) Use of any component part not manufactured or approved
by DESA in combination with a DESA fireplace system.
PROPER INSTALLATION is the most important step in
ensuring safe and continuous operation of the fireplace.
Consult the local building codes as to the particular
requirements concerned with the installation of all factory
built fireplaces. Although grounding may not be required by
code the manufacturer recommends it.
This model fireplace 36LM/RM meets the construction
and safety standards of HUD for application in mobile
homes when installed according to these instructions.
REQUIREMENTS
BEFORE
WARNING: DO NOT INSTALL A FIREPLACE INSERT
IN THIS BOX UNLESS THE MANUFACTURER'S
INSTRUCTIONS WITH THE INSERT SPECIFICALLY
STATE THIS FIREPLACE HAS BEEN TESTED FOR
USE WITH THE INSERT.
This fireplace is intended to be used as a decorative
appliance and is not intended to be used to heat the home.
This wood burning fireplace complies with the UL 127 standard as
a FACTORY BUILT FIREPLACE and is listed and tested by
Underwriters Laboratories Inc.
CAUTION: The structural integrity of the mobile home floor,
and ceiling/roof must be maintained.

SELECTING LOCATION

To determine the safest and most efficient location for the
fireplace, you must take into consideration the following
guidelines:
1. The location must allow for proper clearances (see figures
1 & 2).
2. Consider a location where the heat output would not be
affected by drafts, air conditioning ducts, windows or
doors.
3. A location that avoids the cutting of joists or roof rafters
will make installation easier.
4. An outside air kit is included with this fireplace. For
more details refer to section on outside air kit installation
on page 4.
WARNING: DO NOT INSTALL IN A BEDROOM.
MINIMUM CLEARANCES TO COMBUSTIBLES:
Back and sides of fireplace .......................3/4" Min.
Note: the ¾ " clearance is not required at the nailing flanges
Ceiling to Top of Opening .................... 66-1/4" Min.
Floor* ....................................................0" Min.
*See step 2 of "Installing the Fireplace" – next page
Perpendicular Wall to Opening of Unit ............24" Min.
Top Spacers ..............................................0" Min.
Mantel Clearances ................................. see page 7
"Finishing your Fireplace"
Chimney Outer Pipe Surfaces ........................2" Min.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH
INSULATION OR OTHER MATERIALS.
MINIMUM/MAXIMUM CHIMNEY HEIGHT:
The MINIMUM height of the chimney, measured from the
base of the fireplace to the flue gas outlet of the termination, is
14 feet for straight flue. The MAXIMUM height of any
system is 20 feet. This measurement includes the fireplace,
chimney sections and the height of the termination assembly at
the level of the flue gas outlet (see pg. 6, fig. 14).