GE FHSD720C Installation And User Manual page 35

Fhsd700c series
Table of Contents

Advertisement

GE Security
5.3.8 SETUP: Setup Menu
Minimum Access Code Required: Level 2
Once the Setup Mode is accessed, please follow this procedure to change a parameter:
1. Press Parameter UP & DOWN buttons to reach required SETUP item.
2. Press ENTER.
3. Press Value UP & DOWN buttons to update the item.
4. Press ENTER to update and move to next parameter. If the value is left unchanged, ENTER will
have no effect.
Press MENU to get back to the Main Menu. Press MENU again to get back to Normal display.
The Setup menu has the following items.
Parameter
Value
Defaults
HI RESLTN
0, 1, 2
or 3
OBSC/FT
0 or 1
REMPANEL 0 or 1
REMPOD
0 or 1
DETFLOW
0 or 1
CCODE
Country Code
RES-ISOL
0 or 1
MOD1 to 5
List of available I/O
modules
The FHSD700C detector can operate in a number of different languages. To change the language, the
correct country code (CCODE) must be entered. The software can also be made to swap from metric to
imperial measurements by entering 1 for the United States country code.
www.gesecurity.net
Table 5-6: Setup Menu Parameters and Values
0
Enables the Status Display to show standard resolution (0) or higher Resolution
(1, 2 or 3) for obscuration (switches between a resolution of 0.01 to 0.00001).
Note: It is highly recommended to leave this value at 0. Changing the value from
0 will cause some configuration values to change. Connection to GE Security
fire configuration and management software will automatically change this value
back to 0.
0
Set to 1 to display smoke valve in % obs/ft. Normally % obs/m.
0
Enables remote panel operation. A communications fault will be displayed if this
is enabled without a remote display connected.
0
Set to 1 if a Remote Sensing Unit is connected.
Note: This option is not available for standard FHSD700C devices.
1
In addition to individual sector flow monitoring, detector flow monitoring is also
incorporated.
Set to 1 to enable.
See Table 5-7. Changes metric/imperial units.
1
Set to 1 to reset system with 24 V on reset line.
Set to 0 to isolate system when 24 V is applied for 8 seconds or more.
All I/O modules fitted at build will have this information entered. If additional I/O
modules are installed, their type must be entered here.
Table 5-7: Country Codes for the FHSD700C Series
Language
English (default)
United States (English)
French
Spanish
Portuguese
Italian
German
FHSD700C Series Product Guide
Description
Code
44
1
33
34
35
39
49
29