3.4 Remote Display Panel

An installation kit is available for mounting a display panel up to 1 km away from the detector. It
contains:
 1 Blanking plate
1 Mounting Box
1 Fixing kit
Figure 3-8: Display board and terminal for remotely connecting the Display Panel
Suitable double twisted pair cable for connecting RS485 communications and 24 VDC power can also
be supplied. More information may be found in Installation Guide for RS485 Equipment on page 36.
Ensure that the electrical characteristics of the cable connected are appropriate for the distance
between the detector and display module.
When using the double twisted pair cable, use one pair for RS485 communications, the other pair for 24
VDC supply, and ensure that matching signals are connected at each end.
To use the Display Panel remotely, the main unit must also be configured for remote display operation
by following these steps (please see Figure 5-1 for User Function buttons):
1. Press MENU
2. Use Parameter UP & DOWN to reach SETUP (Scan and Isolate buttons)
3. Press ENTER
4. Enter Level 2 Access Code (693) - please refer to Access Codes on page 18 for details on the
Access Code
5. Use Parameter UP & DOWN to reach REMPANEL
6. If the display shows REMPANEL 0 then press Value UP to get REMPANEL 1
7. Press ENTER
8. Press MENU twice to revert to normal
www.gesecurity.net
FHSD700C Series Product Guide
1.
Jumper Link
2.
RS485
3.
24 VDC power