GE FHSD720C Installation And User Manual page 18

Fhsd700c series
Table of Contents

Advertisement

FHSD700C Series Product Guide
3.2.3 Connection Interfaces
The following tables define input and output connections for the FHSD700C Series.
CN1: RS232 Interface
2
Receive Data
3
Transmit Data
5
0 V
1, 4, 6, 7,
N/C
8, 9
Shell
Earth (Screen)
CN2: DC Supply
1
24 VDC in
2
0 VDC in
3
N/C
4
N/C
5
Mains/Battery
CN3: Auxiliary Supply Output Interface
1
0 VDC
2
24 VDC
CN4: Remote Reset Interface
1
- input
2
+ input
CN6: RS485 Interface
1
Shield
2
RS485 -
3
RS485+
CN7: Output Relay Interface
1
FIRE 2
C
2
NC
3
NO
4
FIRE 1
C
5
NC
6
NO
7
ACTION
C
8
NC
9
NO
10
ALERT
C
11
NC
12
NO
13
FAULT
C
14
NC
15
NO
Note: Connection CN14 is only used for special applications.
12
Table 3-2: Connections for i602 I/O Board
Requires suitable twisted screened cable up to a maximum distance of 15 m.
Requires 16 x 0.25-15 A (18 AWG) cable (0.75mm
for EC).
Note: Link Pin 2 (0 V) and Pin 5 (MAINS/BAT). See External Power Supply Connection on page
9 for further details.
Requires 7 x 0.2 - 6 A (24 AWG) cable (1 A maximum load).
Opto isolated input. 24 VDC low current signal.
Belden 9842 cable (or suitable equivalent)
Note: Ensure that the Mid/End Jumper Link is fitted correctly on pins 7/8/9 of CN 5. Please see
Appendix B.1 on page 36 for further details.
Requires 7 x 0.2 - 6 A (24 AWG) cable
Note: Maximum relay contact rating is 2 A @ 30 VDC.
Note: Please see 4-Channel Relay Module on page 31 for further details.
2
minimum IEC60227 H05 W-F/H05 WH2-F2
www.gesecurity.net