Download Print this page

Complete Refrigerant Piping Connections; Make Electrical Connections - Carrier 24AHA4 Performance Series Installation Instructions Manual

Air conditioner with puron refrigerant 1-1/2 to 5 nominal tons
Hide thumbs Also See for 24AHA4 Performance Series:

Advertisement

COMPLETE REFRIGERANT PIPING CONNECTIONS

Outdoor units may be connected to indoor units using
field−supplied tubing of refrigerant grade and condition. See
Product Data for correct line sizes. Do not use less than 10 ft (3.05
m) of interconnecting tubing.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4
mm) vertical rise to the valve connections on the outdoor
unit. If more than the recommended length is buried,
refrigerant may migrate to cooler, buried section during
extended periods of system shutdown. This causes refrigerant
slugging and could possibly damage the compressor at
start−up.
When more than 80 ft (24.4 m) of interconnecting tubing and more
than 20 ft (6.1 m) of vertical lift is used, consult the residential
Long Line Application Guide for required accessories. If either
refrigerant tubing or indoor coil is exposed to the atmosphere, the
system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary
turns and bends. Suspend refrigerant tubes so they do not damage
insulation on vapor tube and do not transmit vibration to structure.
Also, when passing refrigerant tubes through a wall, seal the
opening so that vibration is not transmitted to structure. Leave
some slack in refrigerant tubes between structure and outdoor unit
to absorb vibration. Refer to separate indoor unit installation
instructions for additional information.
Filter Drier
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from
step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
Fig. 3 - Filter Drier Components
The filter drier must be replaced whenever the refrigeration system
is exposed to the atmosphere.
Only use factory specified liquid−line filter driers with rated
working pressures less than 600 psig.
NOTE: Do not install a suction−line filter drier in liquid line.
Make Piping Sweat Connections
!
Remove plastic caps from liquid and suction service valves. Use
refrigerant grade tubing. Service valves are closed from the factory
and are ready for brazing. After wrapping the service valve with a
wet cloth, the tubing set can be brazed to the service valve using
either silver bearing or non−silver bearing brazing material.
Consult local code requirements. Refrigerant tubing and the indoor
coil are now ready for leak testing.
NOTE: Unit is shipped with Puron (R−410A) refrigerant factory
charge indicated on nameplate.
Pass nitrogen or other inert gas through piping while brazing to
prevent formation of copper oxide.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
To prevent damage to unit or service valves observe the
following:
S Use a brazing shield.
S Wrap service valves with wet cloth or use a heat sink
material.

MAKE ELECTRICAL CONNECTIONS

!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or
death.
The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault should
occur. The ground may consist of electrical wire or metal
conduit when installed in accordance with existing electrical
codes.
!
A05178
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may
cause damage to electrical components. Such operation
would void any applicable warranty.
3
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
WARNING
CAUTION

Advertisement

loading