Basic Installation Hints And Rules - Chamberlain SL 1000-B1 Installation And Operation Instructions Manual

Table of Contents

Advertisement

BASIC INSTALLATION HINTS AND RULES

PLEASE READ THIS SECTION CAREFULLY BEFORE BEGINNING YOUR INSTALLATION.
The sections that follow contain detailed procedures for installation of a model SL 1000-B1 system. In addition
to these specific procedures, there are a number of general hints and rules which will help ensure that your
installation will be done correctly and efficiently. These are discussed below.
1. UNDERSTAND THE SYSTEM AND INSTALLATION SITE THOROUGHLY. The SL 1000-B1 is a flexible
and reliable gate operator system, but the quality of service depends directly on the quality of installation.
Please read these instructions carefully and study the applicable diagrams before planning your
installation. In particular, understand any site characteristics that may affect the system installation.
2. INSTALL PERMANENT WIRING. U.L. specifications require the SL 1000-B1 system to be permanently
wired. Refer to your local wiring code for specific information.
WARNING: Damage caused by faulty wiring is not covered by warranty.
3. GROUND THE SYSTEM. The system contains parts which may be damaged by static discharge. A
proper earth ground connected to the gate operator housing (see Figure 11) will significantly reduce the
chances of damage or improper operation. The shielding in the cables specified for all remote sensors and
controls should also be connected to earth ground at the controller end of the cable only.
To be effective, the ground connection must be made by running 12 awg copper wire to a good ground
point (e.g., an electrical panel, a metallic cold water pipe that runs into the earth, or a grounding rod at least
10 feet in length that is driven into the earth) within 12 feet of the system. Even if you have a good earth
ground, you should try to discharge any static before handling the circuit boards.
WARNING: Damage caused by static discharge and lightning is not covered by warranty.
4. PROVIDE POWER FROM A DEDICATED SOURCE. The outlet into which you connect the Gate
Operator should be wired to its own circuit breaker. This will reduce the line noise introduced into system
power and minimize the risk of having other equipment interrupt system operation. In a Master/Slave
system, Master and Slave must each have separate circuits.
5. DO NOT OVERLOAD THE TERMINAL BLOCKS. The terminal blocks used in the gate operator are
removable and the pins are soldered into the boards. To connect your wires, remove the "head" from the
correct terminals and open the screws. Insert the wire into the correct opening on the front and tighten the
screw until the wire is held firmly. When you have made all connections for a given "head", plug it back
onto the pins designated for that terminal block.
Stranded wire must be between 16 and 24 awg. Solid wire must be between 18 and 24 awg. This is the
total thickness measurement so, if you are putting two wires in, the combined thickness must fall within this
range. NEVER try to insert more than two wires per terminal.
6. ENSURE GOOD CONNECTIONS. A light tug on the wire will tell you if the connection is secure. When
reconnecting system components, make sure all pins are straight on chips, connectors, and terminal block
heads.
7. READ THE MARKINGS CAREFULLY. The connection points are marked on the boards clearly. Before
making any connection, be sure to read the marking and check it against the corresponding figure in these
instructions so that you understand the connection you are making.
8. TRAIN YOUR CUSTOMERS THOROUGHLY. Although customer responsibility is limited to proper
installation, the quality of service is determined by the care of system setup. Ensure that the customer has
a copy of this manual to guide them. It will save you and them lots of inconvenience and aggravation later.
Rev C
WARNING
Doc 6001204 (01-20260)
Page
2 of 40

Advertisement

Table of Contents
loading

Table of Contents