TECHNICAL SUPPORT MANUAL
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING, CAU-
TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only
used on product labels to signify an immediate haz-
ard. The signal words WARNING, CAUTION, and
NOTE will be used on product labels and through-
out this manual and other manuals that may apply
to the product.
DANGER − Immediate hazards which will result in
severe personal injury or death.
WARNING − Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or opera-
tion.
TABLE OF CONTENTS
Model Number Identification
Wiring Diagrams
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging Chart
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tech Labels (Expanded Data)
Cooling Multipying Factors
Heating Multipying Factors
MODELS
C4H318GKD200
H4H318GKD200
C4H324GKD200
H4H324GKD200
C4H330GKE100
H4H330GKE100
C4H336GKE100
H4H336GKE100
C4H342GKE100
H4H342GKE100
C4H348GKE100
H4H348GKE100
C4H360GKD300
H4H360GKD300
Split System Heat Pump
(C,H,T)4H3
Safety Labeling and Signal Words
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
5 − 12
. . . . . . . . . . . . . . . . . .
13 − 17
. . . . . . . . . . . . . . . . .
18 − 22
T4H318GKD200
T4H324GKD200
T4H330GKE100
T4H336GKE100
T4H342GKE100
T4H348GKE100
T4H360GKD300
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this
manual in the following manner:
CAUTION
!
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
WARNING
!
2
DEATH, PERSONAL INJURY, AND/OR PROPERTY
3
DAMAGE HAZARD
4
Failure to carefully read and follow this warning
could result in equipment malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified per-
sons could result in equipment malfunction, prop-
erty damage, personal injury and/or death.
The information contained in this manual is in-
tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with
the proper tools and test instruments.
Installation must conform with local building
codes and with the National Electrical Code
NFPA70 current edition or Canadian Electrical
Code Part 1 CSA C.22.1.
WARNING
428 04 5402 00
May 2010

Advertisement

loading

Summary of Contents for ICP C4H318GKD200

  • Page 1 MODELS erty damage, personal injury and/or death. The information contained in this manual is in- tended for use by a qualified service technician fa- C4H318GKD200 H4H318GKD200 T4H318GKD200 miliar with safety procedures and equipped with C4H324GKD200...
  • Page 2 TECHNICAL SUPPORT MANUAL Split System Heat Pump: (C,H,T)4H3 OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase) Digit Position: 5, 6 Example Part Number: Product Family 4 = R−410A REFRIGERANT A = Air Conditioner H = Heat Pump TYPE 3 = 13 SEER 4 = 14 SEER 5 = 15 SEER 6 = 16 SEER...
  • Page 3 Model Sizes: 18, 24, 30, 36, 42, 48, 60 330751−101_D...
  • Page 4 TECHNICAL SUPPORT MANUAL Split System Heat Pump: (C,H,T)4H3 R−410A CHARGING CHART Rating Plate (required) Subcooling Temperature ° F (° C) ° F (° C) ° F (° C) ° F (° C) ° F (° C) (° C) (° C) Measured Liquid Pressure (psig) R−410A Required Liquid Line Temperature °...
  • Page 5 MULTIPLYING FACTORS (Refer to pages 5−11) † Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 foot (7.6m) line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ††...
  • Page 6 18 Size Outdoor With FS(M,U)4X18 Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 20.50 18.60 17.24 16.89 16.29 19.51 17.69 16.37 16.04...
  • Page 7 24 Size Outdoor With FS(M,U)4X24 Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 26.97 24.65 22.94 22.50 21.73 25.72 23.49 21.84 21.42...
  • Page 8 30 Size Outdoor With FS(M,U)4X30**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 27.76 29.00 29.57 31.74 34.69 26.66 27.62 28.15 30.23...
  • Page 9 36 Size Outdoor With FSU4X36 Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 33.16 33.94 34.54 37.01 40.35 31.86 32.35 32.90 35.27...
  • Page 10 42 Size Outdoor With FS(M,U)4X42**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 39.05 40.45 41.23 44.21 48.26 37.54 38.56 39.29 42.14...
  • Page 11 48 Size Outdoor With FS(M,U)4X48**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 45.85 47.48 48.43 52.07 56.99 43.97 45.13 46.02 49.50...
  • Page 12 60 Size Outdoor With FS(M,U)4X60**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63† † 63†† 63† † 63† † 63† † MBh† 57.36 59.39 60.53 64.73 70.28 55.12 56.60 57.68 61.72...
  • Page 13 COOLING Multiplying Factors for other Indoor Combinations Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model (C,H,T)4H318 *FS(M,U)4X18**** 1.00 1.00 EHD4X24A** *9MPV075 1.05 0.96 FEM4P24**A* 1.02 0.93 ED*4X18B**...
  • Page 14 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X30F** *9MPV050 1.04 0.97 EHD4X30A** *8MPV075 1.04 0.98 FS(M,U)4P30**A* 1.04 1.00...
  • Page 15 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model EHD4X30A** *8MPV050 1.00 1.00 EHD4X36A** *9MPV100 1.00 0.96 FXM4X30**A* 1.00 0.96...
  • Page 16 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X42J** *8MPV100 1.00 0.96 EHD4X42A** *8MPV075 1.00 0.96 FSM4X36**** 1.00 1.00...
  • Page 17 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X48J** *8MPV125 1.00 0.96 EHD4X48A** *8MPV125 1.00 0.96 FVM4X48**** 1.00 0.92...
  • Page 18 HEATING Multiplying Factors for other Indoor Combinations Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model (C,H,T)4H318 *FS(M,U)4X18**** 1.00 1.00 EHD4X24A** *9MVX040 1.00 0.90 FEM4X24**** 0.98 0.91 ED*4X18B**...
  • Page 19 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X30F** *9MPV050 0.96 0.90 EHD4X30A** *8MPV075 0.95 0.88 FS(M,U)4P30**A* 0.98 0.94...
  • Page 20 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model EHD4X30A** *8MPV050 0.98 1.00 EHD4X36A** *9MPV125 0.99 0.95 EHD4X30A** *8MPV075 0.98...
  • Page 21 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X42J** *8MPV100 0.97 0.93 EHD4X42A** *8MPV100 0.97 0.90 FVM4X36**** 0.97 0.95...
  • Page 22 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X48J** *9MPV100 0.99 0.98 EHD4X48A** *9MPV075 0.99 1.00 FXM4X42**A* 0.99 0.97...