TECHNICAL SUPPORT MANUAL
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING, CAU-
TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only
used on product labels to signify an immediate haz-
ard. The signal words WARNING, CAUTION, and
NOTE will be used on product labels and through-
out this manual and other manuals that may apply
to the product.
DANGER − Immediate hazards which will result in
severe personal injury or death.
WARNING − Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or opera-
tion.
TABLE OF CONTENTS
Wiring Diagrams
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging Chart
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tech Labels (Expanded Data)
Cooling Multipying Factors
Heating Multipying Factors
Model Number Identification
MODELS
C4H418GKD200
H4H418GKD200
C4H419GKD100
H4H419GKD100
C4H424GKD200
H4H424GKD200
C4H430GKD200
H4H430GKD200
C4H436GKD200
H4H436GKD200
C4H442GKD200
H4H442GKD200
C4H448GKD200
H4H448GKD200
C4H460GKD300
H4H460GKD300
C4H461GKD100
H4H461GKD100
Split System Heat Pump
(C,H,T)4H4
Safety Labeling and Signal Words
2 − 3
. . . . . . . . . . . . . . . .
5 − 13
. . . . . . . . . . . . . . . . . .
14 − 18
. . . . . . . . . . . . . . . . .
19 − 24
. . . . . . . . . . . . . . . . . . . .
T4H418GKD200
T4H419GKD100
T4H424GKD200
T4H430GKD200
T4H436GKD200
T4H442GKD200
T4H448GKD200
T4H460GKD300
T4H461GKD100
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this
manual in the following manner:
CAUTION
!
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
WARNING
!
PERSONAL INJURY, AND/OR PROPERTY DAM-
4
AGE HAZARD
Failure to carefully read and follow this warning
could result in equipment malfunction, property
damage, personal injury and/or death.
25
Installation or repairs made by unqualified per-
sons could result in equipment malfunction, prop-
erty damage, personal injury and/or death.
The information contained in this manual is in-
tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with
the proper tools and test instruments.
Installation must conform with local building
codes and with the National Electrical Code
NFPA70 current edition or Canadian Electrical
Code Part 1 CSA C.22.1.
WARNING
428 04 5513 00
March 2010

Advertisement

loading

Summary of Contents for ICP C4H418GKD200

  • Page 1 Installation or repairs made by unqualified per- sons could result in equipment malfunction, prop- MODELS erty damage, personal injury and/or death. The information contained in this manual is in- C4H418GKD200 H4H418GKD200 T4H418GKD200 tended for use by a qualified service technician fa- C4H419GKD100...
  • Page 2 Model Sizes: 18, 19, 24, 30, 36, 42, 48, 60 330751−101_D...
  • Page 3 Model Size: 61 330752−101_D...
  • Page 4 TECHNICAL SUPPORT MANUAL Split System Heat Pump: (H,C,T)4H4 R−410A CHARGING CHART Rating Plate (required) Subcooling Temperature ° F (° C) ° F ° F ° F ° F (° C) (° C) (° C) (° C) (° C) (° C) Measured Liquid Pressure (psig) R−410A Required Liquid Line Temperature °...
  • Page 5 MULTIPLYING FACTORS (Refer to pages 6−12) † Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ††...
  • Page 6 18 Size Outdoor With FEM4X18**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 62†† 63†† 63†† 63†† 63†† MBh† 21.03 19.06 17.66 17.31 16.70 20.03 18.13 16.79 16.45 16.02 18.98 17.16 15.86...
  • Page 7 19 Size Outdoor With FEM4X18**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 62†† 63†† 63†† 63†† 63†† MBh† 21.45 19.37 17.89 17.51 16.75 20.42 18.43 17.02 16.66 16.10 19.32 17.43 16.09...
  • Page 8 24 Size Outdoor With FS(M,U)4X30**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 27.78 25.42 23.69 23.23 22.41 26.42 24.18 22.53 22.10 21.50 24.98 22.86 21.30...
  • Page 9 30 Size Outdoor With FSU4X36**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 34.58 31.36 29.06 28.49 27.61 33.01 29.89 27.68 27.15 26.53 31.34 28.35 26.22...
  • Page 10 36 Size Outdoor With FS(M,U)4X42**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 41.90 38.05 35.28 34.58 33.39 40.00 36.30 33.62 32.97 32.10 38.00 34.44 31.87...
  • Page 11 42 Size Outdoor With FS(M,U)4X48**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 49.78 45.61 42.50 41.67 40.18 47.27 43.32 40.37 39.60 38.53 44.62 40.92 38.16...
  • Page 12 48 Size Outdoor With FS(M,U)4X60**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 56.53 51.42 47.69 46.71 45.05 53.78 48.87 45.30 44.38 43.21 50.91 46.24 42.84...
  • Page 13 60 Size Outdoor With FEM4X60**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 70.01 64.42 60.24 59.12 57.11 66.65 61.32 57.34 56.29 54.85 63.02 58.00 54.26...
  • Page 14 61 Size Outdoor With FEM4X60**** Indoor Cooling Outdoor Ambient Temperature − Degrees F, Dry Bulb COOLING Entering Indoor Temperature − Degrees F, Wet Bulb 63†† 63†† 63†† 63†† 63†† MBh† 69.26 63.11 58.68 57.52 55.51 65.96 60.15 55.93 54.87 53.43 62.48 57.00 53.03...
  • Page 15 COOLING Multiplying Factors for other Indoor Combinations Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model (C,H,T)4H418 >FEM4X18**** 1.00 1.00 ED*4X24F** *9MPV075 1.03 0.99 EHD4X24A** MV08B15**B* 1.01 0.96...
  • Page 16 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X24F** 0.99 1.02 EHD4X24A** *9MVX040 1.00 0.96 EHD4X30A** MV08B15**B* 1.02 0.94...
  • Page 17 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X36J** *8MPV100 1.02 0.90 EHD4X36A** *8MPV100 1.03 0.92 (C,H,T)4H436 >...
  • Page 18 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X42F** *9MVX060 0.98 1.00 ED*4X48J** MV16J22**B* 1.01 0.93 EHD4X48A** *9MPV075 1.00...
  • Page 19 COOLING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Indoor Furnace Indoor Furnace Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Capac. (MBh) Power (AMPS) Model Model Model Model Model Model FS(M,U)4X48**** ED*4X48L** 0.99 0.99 EHD4X48A** *9MVX100 0.99 0.99 1.00 1.00 ED*4X60J**...
  • Page 20 HEATING Multiplying Factors for other Indoor Combinations Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Model Model Model Model Model Model (C,H,T)4H418 >FEM4X18**** 1.00 1.00 ED*4X24F** *9MPV075 1.00 0.95 EHD4X24A** MV08B15**B* 1.00 0.99...
  • Page 21 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X24F** 1.00 1.01 EHD4X24A** *9MVX040 1.00 0.97 EHD4X30A** MV08B15**B* 0.98 0.95...
  • Page 22 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X36J** *8MPV100 0.99 0.92 EHD4X36A** *8MPV100 0.99 0.91 (C,H,T)4H436 >...
  • Page 23 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X42F** *9MVX060 0.99 1.04 ED*4X48J** MV16J22**B* 0.98 0.95 EHD4X48A** *9MPV075 1.00...
  • Page 24 HEATING Multiplying Factors for other Indoor Combinations (continued) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Indoor Furnace Capac. (MBh) Power (AMPS) Model Model Model Model Model Model ED*4X48L** 1.00 1.03 EHD4X48A** *9MVX100 1.00 1.03 FS(M,U)4X48**** 1.00 1.04 ED*4X60J**...
  • Page 25 TECHNICAL SUPPORT MANUAL Split System Heat Pump: (H,C,T)4H4 OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase) Digit Position: 5, 6 Example Part Number: Product Family 4 = R−410A REFRIGERANT A = Air Conditioner H = Heat Pump TYPE 3 = 13 SEER 4 = 14 SEER 5 = 15 SEER 6 = 16 SEER...