Terminals and Ports

DC TERMINALS
These terminals connect to the
battery cables and the DC system.
See page 20 for instructions.
CONTROL WIRING TERMINAL BLOCK
These terminals receive control wires for a
variety of functions including generator control.
See pages 26 and 27 for instructions and the
Operator's Manual for more information.
The Terminal Block can be unplugged from the
AC board for convenience. While installed, keep
screws tight and the block itself secured tightly
to the AC board to prevent malfunction.
INVERTER ON/OFF
These terminals receive wires for a manual
on/off switch to control the inverter.
ON/OFF JUMPER
The jumper alongside these terminals overrides
them and turns the inverter on. (See page 25 for
instructions.) With the jumper installed, a switch
cannot turn the inverter off, but the system
display can turn it off or on. The system display
cannot turn it on if the jumper is not installed.
AUX OUTPUT (AUX+/AUX-)
These terminals deliver 12 Vdc up to 0.7 amps
(8.4 watts). The output can be switched on and
off for many functions. The default function is
to drive a cooling fan or the Turbo Fan.
See page 26 for details.
The functions for the AUX output can be
programmed using the system display.
NOTE : The INVERTER ON/OFF Jumper is installed to the ON position during manufacture, but the FXR
inverter is given an external OFF command at the same time. Its initial state is OFF.
900-0168-01-00 Rev A
LED INDICATORS
These indicators display the inverter status and battery voltage.
The three BATTERY LED indicators (green, yellow, and red) are based on
DC voltage, and provide a very general idea of battery state.
The green INVERTER LED indicator shows if the inverting function is on.
The yellow AC IN LED indicator shows if an AC source is present.
The red ERROR LED indicator shows either a Warning or an Error. A
Warning is an alert for a problem that is not severe enough for
shutdown. An Error usually accompanies inverter shutdown.
Figure 5
Terminals, Ports, and Features
Installation
DC and AC
GROUND TERMINALS
These terminals connect to
a grounding system for
both batteries and AC. See
page 17 for instructions.
AC TERMINAL BLOCK
These terminals receive AC
input and output wires. See
page 23 for instructions.
XCT+/XCT-
Non-operational terminals.
Do not connect anything
to them.
MATE/HUB and RTS PORTS
These ports receive the RJ45
and RJ11 plugs from the
system display and Remote
Temp Sensor. See page 25
for instructions.
The ports are mounted
sideways. When viewed from
the left side, they appear as
shown below.
AUX LED INDICATOR
Orange LED indicator turns on when
12 Vdc output is present.