Maintenance procedures — END OF SEASON
the valve does not weep after the line has had time to drain. If the
valve weeps, lift the seat again to attempt to clean the valve seat.
If the valve continues to weep afterwards, contact your qualified
service technician to inspect the valve and system.
4. If water does not flow from the valve when you lift the lever
completely, the valve or discharge line may be blocked. Immedi-
ately shut down the boiler, following the operating instructions
on page 9. Call your qualified service technician to inspect the
boiler and system.
END OF SEASON MAINTENANCE
To continue operation for DHW
1. If the boiler is to supply heat for domestic hot water generation
during the summer, no changes should be needed. Just leave the
boiler power on and allow the DHW storage tank to call for heat
as necessary.
2. Set back room thermostats to prevent any unnecessary call for
heat during the off season.
12
-
fired water boiler
To leave boiler in stand-by mode
1. The SlimFit boiler's Sola control provides effective features for
stand-by operation, including automatic operation to reduce
freeze possibilities. The Sola control must be setup as needed to
operate the necessary pumps.
2. Leave the boiler power on and allow the Sola control to monitor
the boiler and system during the stand-by period.
The Sola control must be configured to operate all
pumps needed to ensure the system and all circuits will
be protected against freezing. See the SlimFit Boiler
manual for details.
3. Set back room thermostats to prevent any unnecessary call for
heat during the off season.
To shut down the boiler
1. Follow "TO TURN OFF GAS TO APPLIANCE" of the Operat-
ing Instructions, Figure 1, page 4.
2. DO NOT drain the system unless exposure to freezing tempera-
tures will occur.
3. DO NOT drain the system if it is filled with an antifreeze solution.
4. DO NOT shut down boilers used for domestic water heating.
They must operate year-round.
— User's Manual
Part number 550-100-117/0714