Venting
Non-Condensing vent options: CAT I
Vertical negative draft venting system - see page 19.
G
Units that may be vented with a Category I, Type "B" vent material operate with limited burner modulation.
These units can be identified by the Category I and the control number F9 or B9 as noted on the unit's rating
plate. These are the only units that can be vented with standard double-wall vent material. See the General
CAT I
Venting and the Negative Draft General Venting on pages 21 and 22. The flue must terminate at the rooftop and
follow the clearance requirements on pages 27 and 28. Combustion air is supplied from the equipment room.
The installation of the vent must conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1, in
Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
The negative draft in a conventional vent installation must be within the range of 0.02 to 0.08 inches w.c. to
ensure proper operation. Make all draft readings while the unit is in stable operation (approximately 2 to 5
minutes).
PB/FN0502-F9
PB/FN0752-F9
PB/FN1002-F9
PB/FN1302-F9
DirectAire vertical venting with vertical air inlet - see page 19.
H
Units that may be vented with a Category I, Type "B" vent material operate with limited burner modulation.
These units can be identified by the Category I and the control number F9 or B9 as noted on the unit's rating
plate. These are the only units that can be vented with standard double-wall vent material. See the General
CAT I
Venting and the Negative Draft General Venting sections on pages 21 and 22. The flue must terminate at the
rooftop and follow the clearance requirements on pages 27 and 28. Combustion air is supplied vertically
from the rooftop. The installation of the vent must conform to the latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning
Appliances and Equipment. The negative draft in a conventional vent installation must be within the range of
0.02 to 0.08 inches w.c. to ensure proper operation. Make all draft readings while the unit is in stable operation
(approximately 2 to 5 minutes).
MODEL
PB/FN0502-F9
PB/FN0752-F9
PB/FN1002-F9
PB/FN1302-F9
DirectAire vertical with sidewall air inlet - see page 19.
I
Units that may be vented with a Category I, Type "B" vent material operate with limited burner modulation.
These units can be identified by the Category I and the control number F9 or B9 as noted on the unit's rating
plate. These are the only units that can be vented with standard double-wall vent material. See the General
CAT I
Venting and the Negative Draft General Venting sections on pages 21 and 22. The flue must terminate at the
rooftop and follow the clearance requirements on pages 27 and 28. Combustion air is supplied horizontally
from the outside. The installation of the vent must conform to the latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning
Appliances and Equipment. The negative draft in a conventional vent installation must be within the range of
0.02 to 0.08 inches w.c. to ensure proper operation. Make all draft readings while the unit is in stable operation
(approximately 2 to 5 minutes).
MODEL
PB/FN0502-F9
Air Inlet Cap
PB/FN0752-F9
PB/FN1002-F9
PB/FN1302-F9
20
FIELD PROVIDED TERMINATIONS
MODEL
VENT SIZES
FIELD PROVIDED TERMINATIONS
AIR SIZES
VENT SIZES
5"
5"
6"
6"
AIR
VENT
SIZES
SIZES
5"
7"
5"
9"
6"
10"
6"
12"
TABLE - 2I
MODEL
7"
PB/FN1501-B9
9"
PB/FN1701-B9
10"
PB/FN2001-B9
12"
TABLE - 2J
MODEL
7"
PB/FN1501-B9
9"
PB/FN1701-B9
10"
PB/FN2001-B9
--
12"
TABLE - 2K
AIR INLET CAP
KIT
MODEL
NUMBER
SAK3003
PB/FN1501-B9
SAK3003
PB/FN1701-B9
SAK3004
PB/FN2001-B9
--
SAK3004
Installation & Operation Manual
VENT SIZES
12"
14"
14"
--
AIR SIZES
VENT SIZES
6"
7"
8"
--
AIR
VENT
SIZES
SIZES
6"
12"
7"
14"
8"
14"
--
--
--
12"
14"
14"
--
KIT
NUMBER
SAK3004
SAK3005
SAK3006
--