SIEMENS Model CP-2ER CONNECTION DIAGRAM
N O CYLINDER SUPERVISORY
SWITCH, P/N 500-878709
N C ABORT STATION
MODEL AW-1
MANUAL DISCHARGE
STATION MODEL MH-51
5.6K
W,
1/2W EOL
MANUAL DISCHARGE
PRESSURE SWITCH, P/N 500-486536
-
1.78K
W
1/2W EOL
P/N 140-016124
+
NOTE:
Both zones 1
-
and 2 may be
connected
as either
+
Class A or
Class B.
TYPICAL CONNECTION TO FIRE ALARM SYSTEM
(When CP-2ER panels are arranged for NFPA Releasing Service)
CP-2ER
ALARM
5
6
TO LISTED
FIRE ALARM
CONTROL
PANEL
TROUBLE CONTACTS MUST BE CONNECTED AS SHOWN
SO AS NOT TO INTERFERE WITH AN ALARM CONDITION.
Technical Manuals Online! - http://www.tech-man.com
2.2K
W,
RATED 15 VDC
1/2W EOL
3.4mA SUPV
RATED 15 VDC
1.5mA SUPV
RATED 15 VDC
1.8mA SUPV
ZONE 2
INITIATING CIRCUIT
RATED 17.6 - 22.5 VDC
SUPV 12mA
ALARM 120mA
CLASS B CONNECTION
ZONE 1
INITIATING CIRCUIT
RATED 17.6 - 22.5 VDC
SUPV 12mA
ALARM 120mA
CLASS A CONNECTION
1.78K
W
1/2W EOL
P/N 140-016124
TROUBLE
ALARM
TROUBLE
1
3
5
6
1
DISCHARGE
CIRCUIT RATED:
24VDC, SUPV. 1.4mA
ALARM 2.0A MAX
TB1
TB2
14
6
+
-
13
5
12
4
+
-
11
3
DISCHARGE AUDIBLES
10
2
-
+
9
1
GENERAL ALARM AUDIBLES
8
7
6
5
4
3
2
1
CP-2ER
Charging Current Normal: 300mA, 24 VDC
3
Charging Current Max:
Load Current Max:
EOL
DEVICE
24 HR: P/N 175-084476 (5 AH)
60 HR: P/N 175-084477 (10 AH)
DISCHARGE DEVICE:
REFER TO AGENT DISCHARGE
DEVICES TABLE
IF THIS CIRCUIT IS NOT USED,
CONNECT A 1K, 1W RESISTOR
ACROSS THE TERMINALS
24 VDC LISTED POLARIZED
AUDIBLE DEVICES
AUDIBLE CIRCUITS
19 VDC (MIN), 28 VDC (MAX)
SUPV 1.2mA
ALARM 1.5A MAX
POWER SUPPLY
1
INPUT: 120V,
50/60 HZ, 2A MAX
2
NEUTRAL
3
BATTERIES 24 VDC
560mA
3.3A
4.0A with self-
interrupting solenoid,
P/N 500-890181
5.6K , 1/2W EOL
W
RESISTORS
P1
P2