Filter Sign Setting - Toshiba MMK-AP0074MH-E Installation Manual

Hide thumbs Also See for MMK-AP0074MH-E:
Table of Contents

Advertisement

SMMS High-Wall Type
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers start
swinging. The indoor unit for change settings can be
confirmed.
3
Specify CODE No.[
/
buttons.
4
Select SET DATA [
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
2
from Procedure
.
• To change other settings of the selected indoor
unit, repeat from Procedure
Use
button to clear the settings.
To make settings after
repeat from Procedure
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, "SETTING" flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
] with "TEMP."
] with "TIME"
3
.
button was pushed,
2
.
– 28 –

Filter sign setting

According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No.. in Procedure
• For the SET DATA in Procedure
SET DATA of filter sign term from the following
table.
SET DATA
0000
0001
150 H (Factory default)
0002
0003
0004
To secure better effect of heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator, etc. to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No.. in Procedure
• For the SET DATA in Procedure
SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Detection temp shift value
0000
0001
0002
+2 °C (Factory default)
0003
0004
0005
0006
Installation Manual
6
).
3
, specify [01].
4
, select the
Filter sign term
None
2500 H
5000 H
10000 H
6
).
3
, specify [06].
4
, select the
No shift
+1 °C
+3 °C
+4 °C
+5 °C
+6 °C
EN
28-EN