Electric Wiring Work - Daikin FXSQ20M8V3B Installation And Operation Manual

Vrv system air conditioner
Table of Contents

Advertisement

Caution for drain socket
Do not remove the drain pipe plug. Water might leak out.
The drain outlet is only used to discharge water if the drain
pump is not used or before maintenance. Gently put in and
out the drain plug. Excessive force may deform the drain
socket of the drain pan.
Pulling out the plug
1
Drain plug
Do not wiggle the plug up and down
Pushing in the plug
1
Drain plug
2
Philips screwdriver
Set the plug and push it by using a Philips screwdriver
When electric wiring work is finished
Check drainage flow during COOL running, explained in
on page
8.
When electric wiring work is not finished
Remove the switch box cover and connect the single-phase power
supply and the remote controller to the terminals. (Refer to
wiring work" on page 5
for switch box attachment/detachment.)
(Refer to
figure 11a
and
figure
1
Switch box cover
2
Power supply wiring port
3
Transmission wiring port
4
Wiring diagram
5
Switch box
6
Plastic clamp
7
Remote controller wiring
8
Terminal board for unit transmission wiring
9
Power supply wiring
10
Indoor PC board
11
Power supply terminal board
12
Earth screw
13
Transmission wiring between units
14
Adaptor for PC board
Next, press the inspection/test operation button
controller. The unit will engage the test operation mode. Press the
operation mode selector button
. Then, press the on/off button
pump will start up. Check that the water has drained from the unit.
Press
to go back to the first mode.
TEST
Installation and operation manual
5
1
1
2
"Test operation"
11b)
on the remote
TEST
until selecting fan operation
. The indoor unit fan and drain
E
LECTRIC WIRING WORK
General instructions
All field supplied parts and materials and electric works must
conform to local codes.
Use copper wire only.
Follow the "Wiring diagram" attached to the switch box cover to
wire the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the
entire system must be installed.
This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.
Electrical characteristics
Model
FXSQ20~125
Model
FXSQ20~32
FXSQ40
FXSQ50
FXSQ63
FXSQ80
FXSQ100
FXSQ125
"Electric
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
NOTE
For details, refer to "Electrical data".
Specifications for field supplied fuses and wire
Model
FXSQ20~125
Model
FXSQ20~125
NOTE
For details, refer to
Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:
1.
Outdoor unit - indoor unit: max. 1000 m (total wiring length: 2000 m)
2.
Indoor unit - remote controller: max 500 m
Hz
Volts
Voltage range
50
230
min. 198-max. 264
power supply
Fan motor
MCA
MFA
KW
0.5
16 A
0.05
0.6
16 A
0.065
0.9
16 A
0.085
1.1
16 A
0.125
1.3
16 A
0.135
1.5
16 A
0.135
2.0
16 A
0.225
Power supply wiring
Field fuses
Wire
16 A
H05VV-U3G
Wire
Sheathed wire (2)
0.75-1.25 mm
"Wiring example" on page
FXSQ20~125M8V3B
VRV System air conditioners
FLA
0.4
0.5
0.7
0.9
1.0
1.2
1.6
Size
Local codes
Size
2
6.
4PW25083-1C