Download Print this page

LST 2251TEM Specification Sheet

Lst multisensor specification sheet

Advertisement

Quick Links

Multisensor
2251TEM
• ADM loop technology with
System Sensor/200 protocol
• Combination of optical and thermal
characteristics of fi re
• Two self-learning and three fi xed
sensitivity levels
• Thermal-only operation
• Constant response sensitivity
• Function testable with magnet
Description
The addressable Multisensor 2251TEM uses the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of fi re in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of fi re.
The sensitivity of the detector can be individually adjus-
ted in 5 steps between 1.5%/m and 5.2%/m according
to the application. Three steps have a fi xed sensitivity,
whereas two self-learning steps automatically adjust the
sensitivity to short-term changes of the environmental
conditions. Furthermore, the optical detection unit can
be completely disabled for a thermal-only operation.
The proven ADM loop technology with System Sen-
sor/200 protocol establishes a permanent communi-
Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
cation between the fi re detection control panel and the
detector. That ensures a periodical function testing of
the detector.
The infl uence of contamination on the optical measu-
rement system is compensated for by using intelligent
evaluation algorithms. With that, the response sensiti-
vity of the detector is kept constant for a long time –
a further effective step to avoid false alarms.
The two LEDs with 360° visibility indicate the activated
condition of the detector. The detector address is se-
lected with two decadic rotary switches, thus allowing
to change the detector without additional tools.
A detector function test can be conveniently conducted
using a magnet. The detector can be attached to va-
rious bases and it can be protected against theft.
A
2251TEM_DBL_LST_EN_0819.PDF • PAGE 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 2251TEM and is the answer not in the manual?

Questions and answers

Summary of Contents for LST 2251TEM

  • Page 1 • Constant response sensitivity • Function testable with magnet Description The addressable Multisensor 2251TEM uses the scattered light principle as well as a separate thermal detection unit. It was developed to detect the charac- teristics of fi re in a wide range of applications, and to avoid deceptive alarms.
  • Page 2 Order name Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED Supply through loop voltage typ. 250µA (quiescent) 57°C (maximum-heat component)