Download Print this page

LST Isolator Module ISM1-3 Specifications

Isolator module

Advertisement

Quick Links

Isolator Module
ISM1-3
• Safe disconnection of a faulty loop
section
• For use in an Apollo/Discovery loop
• Installation in commercial installation
boxes or in the LST standard grid
• Small design
Description
The Isolator Module ISM1-3 is used on the ADM loop with
Apollo/Discovery protocol and disconnects the loop in
the event of a short circuit of the loop connection.
Thereby only the loop elements located between two
isolator modules are affected by the short circuit.
Specifi cations
Operating voltage
Current consumption
Ambient temperature
Dimensions L × W × H
Weight
Approval
Order number
Order name
Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
The Fire Detection Control Panels Series BC216 report
the affected loop elements as faulty and operate the
remaining loop sections, which are not faulty, from both
ends of the loop, until the fault is removed.
Supply through loop voltage
max. 0.2mA
-5°C to +50°C
70 × 24 × 15 (mm)
20g
VdS G296012
249029
Isolator Module/Anal./Apo ISM1-3
A
ISM1-3_DBL_LST_EN_0804.PDF • PAGE 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Isolator Module ISM1-3 and is the answer not in the manual?

Questions and answers