Section 4: Installation Consideration A. Hearth Requirements - Quadra-Fire Millennium 31M-ACC-MBK Owner's Manual

3100 wood stove series automatic combustion control (acc)
Table of Contents

Advertisement

3100 Wood Stove Series (ACC)
4
Installation
A. Hearth Protection Requirements
FLOOR PROTECTION: Floor protector must be non-com-
bustible material, extending beneath heater and to the front,
sides and rear as indicated. The fl oor must be non-com-
bustible or otherwise adequately protected from radiant heat
given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible fl oor is
not suffi cient.
For the Millennium | Limited Edition Models In US instal-
lations, it is necessary to install a fl oor protector of a minimum
of 3/8 inch (9.5mm) thick metal clad millboard or equivalent a
minimum of 16 inches (406mm) in front of glass and 8 inches
(203mm) to both sides of the fuel loading door. Open the
door and measure 8 inches (203mm) from the side edge of
the opening in the face of the appliance. *See exception.
Millennium | Limited Edition Models
Fuel loading door
16 in. from glass
31-5/8 in.
minimum
Figure 12.1
203mm (8 in.)
203mm
(8 in.)
457mm (18 in.)
1041mm (41 in.)
minimum
Figure 12.2
Page 12
39 in.
minimum
8 in.
USA
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
203mm
(8 in.)
1260mm
(49-5/8 in.)
minimum
CANADA
In Canada, similar fl oor protection must be provided 18
inches (457mm) in front and 8 inches (203mm) from the
sides and rear of the stove. *See exception.
*EXCEPTION: Non-combustible fl oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 12.2.
Fire Risk.
Hearth pads must be installed exactly as specifi ed
High temperatures or hot embers may ignite concealed
combustibles.
Corner hearth pad dimensions
with single wall pipe
Figure 12.3
Corner hearth pad dimensions
with double wall pipe
Figure 12.4
NOTE: Corner hearth pad dimensions are based off of 18" min. clear-
ance for single wall pipe, 6" min. for double wall pipe, OR unit tested
safety clearances to combustibles whichever is greater.
7033-277N
WARNING
52-1/2 in.
33-1/4 in.
USA
51 in.
31-3/4 in.
August 3, 2015