Domestic side (tank) piping
Verify
NOTICE
temperature and pressure relief valve
complies with local codes.
combination temperature and pressure
relief valve does not comply with local
codes, replace it with one that does.
Follow the installation instructions in
this section.
Do not place a valve between the combination T&P relief
valve and the tank.
Determine T&P relief valve size by the following
specifications, unless they conflict with local codes:
-
SIT030/040/050 - 3/4" NPT with a minimum CSA
Rating of 105,000 Btu/hr.
-
SIT065/080/119 - 3/4" NPT with a minimum CSA
Rating of 200,000 Btu/hr.
The Lochinvar SIT series water heaters
NOTICE
will absorb/store less than 200,000 Btu/
hr
when
temperature is 210°F and boiler water
supply temperature is 240°F. Listed
outputs are based on ASME Section VIII
Interpretation VIII-1-86-136. Check
with local codes for applicability.
Table 4A
Minimum Relief Valve (CSA Rating)
Model
SIT030
SIT040
SIT050
SIT065
SIT080
SIT119
that
the
combination
If the
domestic
water
outlet
Btu/hr
105,000
105,000
105,000
200,000
200,000
200,000
Installation & Operation Manual
(continued)
Standard installation
Install the T&P relief valve in the connection marked
"Relief Valve".
T&P relief valve discharge piping
T&P relief valve discharge piping MUST be:
- made of material serviceable for a temperature of
250°F or greater.
- directed so that hot water flows away from all persons.
- directed to a suitable place for disposal.
- installed so as to allow complete draining of the T&P
relief valve and discharge line.
- terminated within 6" of the floor.
T&P relief valve discharge piping MUST NOT be:
- excessively long. Using more than two (2) elbows or
15 feet of piping can reduce discharge capacity.
- directly connected to a drain. Refer to local codes.
- subject to freezing.
Do not install any valve between the T&P
WARNING
relief valve and the tank connection or
on the T&P relief valve discharge piping.
Improper placement and piping of T&P
relief valve can cause severe personal injury,
death or substantial property damage.
The T&P relief valve is not intended for
CAUTION
constant duty, such as relief of pressure
due to repeated normal system expansion.
Correct this condition by installing a
properly sized expansion tank in a domestic
water system. Refer to the expansion tank
manufacturer's installation instructions for
proper sizing.
Failure to install and maintain a new, listed
WARNING
3/4" X 3/4" T&P relief valve will release
the manufacturer from any claim which
might result from excessive temperature
and pressures.