Faults, causes and
rectification
Pump doesn't run when power is
switched on :
■ Check solar control unit for correct settings and tight wire
connections.
■ Check fuses.
■ Check pump voltage, refer to the pump rating plate for
requirements.

Motor blocked:

■ Close shut-off instruments upstream and downstream of
pump at high liquid temperatures and system pressures.
Allow pump to cool first.
■ Fully unscrew bleed screw and check ease of movement of
pump rotor by turning the slotted shaft end with a
screwdriver; use force to turn if necessary.

Pump Noise:

■ In the event of cavitation caused by insufficient inlet
pressure, increase primary system pressure within allowable
range.
■ Check speed setting.
If the fault cannot be rectified, please contact your nearest
Lochinvar/TiSUN customer service representative.