Napoleon GD40-N Installation And Operation Instructions Manual
Napoleon GD40-N Installation And Operation Instructions Manual

Napoleon GD40-N Installation And Operation Instructions Manual

Gas fired - direct vent millivolt system

Advertisement

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA-2.22 AND ANSI Z21.50 RESPECTIVELY FOR VENTED GAS FIREPLACE.
GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
Installation and service must be performed by a qualified installer, service agency
Fax: (705)722-6031 Email: ask@napoleon.on.ca
Web: www.napoleon.on.ca
INSTALLATION AND OPERATION INSTRUCTIONS FOR
MULTI-VIEW DECORATIVE FIREPLACE
NATURAL GAS MODEL
PROPANE GAS MODEL
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / AGA / CGA METHODS

FOR YOUR SAFETY

this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

or the gas supplier.
Wolf Steel Ltd., RR#1, 9 Napoleon Rd.,
Barrie, ON., Canada L4M 4Y8 (705)721-1212
R-2000
GD40-N
GD40-P
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas suppli-
er's instructions.
• If you cannot reach your gas supplier, call
the fire department.
1
WS-415-091 / 06.26.00

Advertisement

Table of Contents
loading

Summary of Contents for Napoleon GD40-N

  • Page 1: For Your Safety

    • If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Wolf Steel Ltd., RR#1, 9 Napoleon Rd., Barrie, ON., Canada L4M 4Y8 (705)721-1212 Fax: (705)722-6031 Email: ask@napoleon.on.ca R-2000 Web: www.napoleon.on.ca...
  • Page 2: Table Of Contents

    TABLE of CONTENTS Pg 4-5 INTRODUCTION PG 16-20 VENTING SPECIFICS Warranty Horizontal Venting Installation General Instructions Vertical Venting Installation General Information Fireplace Vent Connection Care of Glass & Plated Parts Gas Supply Connection 6-10 VENTING 20-22FINISHING Vent Lengths Mantle Height Locations Venting Options Log Placement/Charcoal Embers Mobile Home Installation...
  • Page 3 RIGHT OPEN END MODEL SEE-THRU MODEL LEFT OPEN END MODEL PENINSULA MODEL WS-415-091 / 06.26.00...
  • Page 4 After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered by this warranty.
  • Page 5: General Instructions

    The glass is 3/16" ceramic extending the full width and depth. glass available from your Napoleon / Wolf Steel Ltd. dealer. If the optional heat circulating blower is installed, the blower Do not substitute materials.
  • Page 6: Venting

    The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it Use only Napoleon or Simpson Dura-Vent Model DV-GS is unobstructed and undamaged. venting components. Minimum and maximum vent lengths,...
  • Page 7: Venting Options

    INCLUDE THE FIRST ELBOW DIRECTLY OFF THE UNIT.) horizontal run is required, the fireplace must have a mini- Only the following Napoleon Vent Kits, used in combina- mum vertical rise immediately off the fireplace of 57 inches. tion with each other can be used: FIGURES 4a-c.
  • Page 8 VENTING OPTION #3 Use this chart to calculate vertical rise for horizontal run between 3 feet (maximum length when the vertical rise is at its minimum of 1 foot) and 18 feet. FIGURES 7. 18 FT MAX (3 FT MAX) FIGURES 7 20 FT MAX 1 FT MIN...
  • Page 9: Mobile Home Installation

    VENTING OPTION #5 Use this chart to calculate the total vertical rise required 34 FT MAX when the horizontal run is between 18 feet maximum or 3 feet maximum length when the initial vertical rise is at its (1 FT MAX) minimum of 1 foot.
  • Page 10 AIR TERMIN TERMIN TERMIN TERMINAL INST AL INST AL INST AL INSTALLA ALLA ALLATIONS: ALLA TIONS: TIONS: TIONS: TERMIN AL INST ALLA TIONS: FIGURE 10 INSTALLATIONS CANADIAN U.S.A. 12 INCHES 12 INCHES Clearance above grade, veranda porch, deck or balcony. 12 INCHES 9 INCHES Clearance to windows or doors that open.
  • Page 11: Peninsula Installation Procedure

    PENINSULA INSTALLATION PROCEDURE VENTING COUNTERTOP / BAR INSTALLATION Refer to page 16-19. The first 2 feet of outer 7 inch diam- When finishing the fireplace, a combustible material may eter vent pipe from the appliance or from the unit to the first rest directly on top of the fireplace extension frame.
  • Page 12: Brick Panel Installation

    FACING BRICK PANEL INSTALLATION Combustible materials may be installed flush with the front Insert the side panel and install the retaining brackets at of the fireplace but must not cover any of the black face- either side to secure the panel. Install the remaining pan- areas of the fireplace.
  • Page 13: Open End Installation Procedure

    OPEN END INSTALLATION PROCEDURE VENTING BRICK PANEL INSTALLATION Refer to page 16-19 for venting specifics. The first 2 feet of Start by inserting the top of the rear panel into the brick outer 7 inch diameter vent pipe from the appliance or from holder as illustrated.
  • Page 14 FACING Combustible materials may be installed flush with the front of the fireplace but must not cover any of the black face- areas of the fireplace. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas. DRYWALL DRYWALL It is not necessary to install a hearth extension with this fireplace system.
  • Page 15: See-Thru Installation Procedure

    SEE-THRU INSTALLATION PROCEDURE VENTING Refer to page 16-19 for venting specifics. The first 2 feet of outer 7 inch diameter vent pipe from the appliance or from the unit to the first firestop spacer (whichever distance is less) must be wrapped in the 1 inch thick insulation sleeve (supplied) as well as having a 1 inch air gap.
  • Page 16: Wall And Ceiling Protection

    VERTICAL INSTALLATION: This application occurs when low the venting instructions exactly. venting through a roof. FIGURE 2. Installation kits for vari- ous roof pitches are available from your Napoleon dealer. See Accessories to order the specific kit required. HORIZONTAL INSTALLATION: 1.
  • Page 17: Using Flexible Vent Components

    USING FLEXIBLE VENT COMPONENTS All horizontal runs must have a minimum 1 inch rise per foot using flexible venting. FIGURE 30 For safe and proper operation of the fireplace, follow the venting instructions exactly. HORIZONTAL AIR TERMINAL INSTAL- LATION 1. Stretch the 4" diameter aluminium flexible liner to the required length taking into account the additional length needed for the finished wall surface.
  • Page 18: Vertical Venting Installation

    VERTICAL VENTING INSTALLATION Spacers are attached to the 4" inner flex liner at prede- termined intervals to maintain a 1-1/4" air gap to the 7" FIGURE 31 outer liner. These spacers must not be removed. 1. Fasten the roof sup- 7.
  • Page 19: Using Rigid Vent Components

    The vent system must be supported approximately every 3 jurisdiction or the optional roof support. feet for both vertical and horizontal runs. Use Napoleon vent spacers WS-615-33 or equivalent every 3 feet and 3. Apply high temperature sealant to the outer edge of the either side of each elbow to maintain the minimum 1¼"...
  • Page 20: Gas Supply Connection

    GAS SUPPLY CONNECTION 4. Install the rigid black pipe, ½" type-L copper tubing or, if local codes permit, a " flex connector and shutoff valve 1. Move the fireplace into position and secure to the floor to the gas line and the fireplace gas valve. Seal and tighten using #10 hex head screws (not supplied).
  • Page 21 Use only certified PHAZER logs, glowing embers and charcoal Align logs #4a and #4b nose to nose (39g). embers available from your Napoleon / Wolf Steel Ltd. dealer. WS-415-091 / 06.26.00...
  • Page 22 Side door trim is not required for the end door. FIGURE 40 OPTIONAL LOUVRES: The louvres are installed as il- lustrated in FIGURES 42. Optional plated door trim is also available at your local Napoleon / Wolf Steel dealer. FIGURES 42 FIGURES 41 LOUVRE BRACKETS AND DOOR INSTALLATION: Attach all louvre brackets as required with louvre securing tabs facing out.
  • Page 23: Optional Blower Installation

    OPTIONAL BLOWER INSTALLATION The blower bracket contains slots that allow the blower to INSTALLATION TO BE DONE BY A QUALIFIED IN- be positioned away from the intended gas supply hole. STALLER and must be electrically connected and grounded in accordance with local codes. In the absence of local Secure the blower using the lock washers and wing nuts codes, use the current CSA C22.1 C provided.
  • Page 24: Operation / Maintenance

    A 5 to 10 second total light-up period is satisfactory. If 1. In order to properly clean the burner and pilot assembly, ignition takes longer, consult your Napoleon dealer / distributor. remove the logs to expose both assemblies.
  • Page 25: Adjustments

    Contact your dealer or the factory for questions concerning prices and policies on replacement parts. Normally all parts 1. Model & Serial Number of the unit. can be ordered through your Napoleon dealer or distribu- 2. Installation date of the unit. tor.
  • Page 26: Replacement Parts

    END BRICK PANEL GD-500.106/GD-500.136 GA-GD-475.158 RIGHT BRICK PANEL GA-GD-475.157 LEFT BRICK PANEL GD-500.106 FIRE STOP SPACER GD-500.136 FIRESTOP SPACER WS-385-33 NAPOLEON LOGO GA-GD-500.103 TERMINAL EXTENSION PLATE GA-GD-361.027 INSULATION SLEEVE GA-GD-361.027 WS-573-008 HIGH TEMP SEALANT GA-GD-080.23 UPPER LOUVRE BRACKET GA-GD-010.423 WS-430-001 CERAMIC MAGNET GA-GD-500.103...
  • Page 27: Vent Kits

    PART NO. DESCRIPTION WS-455-4 COMPONENTS UNIQUE TO PENINSULA UNIT: WS-455-03 WS-430-001 CERAMIC MAGNET GD-100.048 GA-GD-135.067 LOG #6 WS-455-027 GD-100.049 WS-300-027 END DOOR GLASS ONLY WS-455-028 GD-010.540 END DOOR GLASS C/W GASKET WS-300-20 SIDE DOOR GLASS ONLY WS-100-042 GA-GD-225.36 BLACK SIDE DOOR FRAME GA-GD-225.045 BLACK END DOOR FRAME GA-GD-322K...
  • Page 28: Accessories

    ACCESSORIES: WS-690-1 MILLIVOLT THERMOSTAT GD301 HEAT GUARD GD303 VINYL SIDING SHIELD WS-573-008 WS-573-008 HI-TEMP SEALANT GD-301 GA-GD-010.370 WALL SUPPORT ASSEMBLY GD225-K DOOR FACIA - BLACK side door only GD225-PB DOOR FACIA - POLISHED BRASS side door only GZ-550-1KT GD250K WEBBED DOOR FACIA GZ-550-1KT BLOWER KIT WS-175-053...
  • Page 29: Trouble Shooting Guide

    TROUBLE SHOOTING GUIDE EFORE ATTEMPTING TO TROUBLESHOOT PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED SYMPTOM PROBLEM TEST SOLUTION Main burner flame Blockage in vent. - remove blockage. In really cold conditions, ice buildup may occur is a blue, lazy, on the terminal and should be removed as required.
  • Page 30 SYMPTOM PROBLEM TEST SOLUTION Pilot burning; no Themostat or switch is de- - connect a jumper wire across the wall switch terminals; if main main fective. burner lights, replace switch / thermostat. burner; gas knob Wall switch wiring is defec- - disconnect the switch wires from the valve &...
  • Page 31 Wolf Steel Fireplace Service History This fireplace must be serviced at least annually depending on usage. Service Technician Date Dealer Name Service Performed Special Concerns Name...
  • Page 32 NOTES: WS-415-091 / 06.26.00...