Contractor Level - Wolf ART Installation And Operating Instrictions

Analog room thermostat with day program for gas fired boilers
Table of Contents

Advertisement

Contractor level

Contractor level
Pressing key changes the display to contractor
level.
The contractor level is segregated into display
and parameter mode.
Individual displays (e.g. A:01) and parameters
(e.g. P:01) are shown in sequence after
pressing
.
In parameter mode you can change the values
displayed above the r.h. rotary selector.
List of displays and parameters
Display list:
Index
Explanation
A 01
Set flow temperature
A 02
Actual flow temperature
A 03
Actual DHW temperature
Parameter list
Index
Explanation
P 03
Set DHW temperature
P 04
Pasteurisation
GB 01
Flow temperature hysteresis
GB 04
Upper fan speed - central heating
GB 05
Frost protection outside temperature
GB 06
Heating circuit pump mode
GB 07
Heating circuit pump run-on
GB 08
Maximum set flow temperature
GB 09
Cycle block
GB 13
Input 1
GB 14
Output 1
GB 15
DHW cylinder hysteresis
Note: Parameters GB01 to GB15 are not avaliable for all boilers; for descriptions see the
installation instructions of the relevant boiler.
Parameters GB 01 - 15 must only be modified by a heating contractor. Incorrect operation
Warning
can lead to system faults.
Parameter 5 (outside temperature frost protection) is only effective with an outside
temperature sensor.
10
Display mode
e.g. actual flow
temperature
Unit
°C
°C
°C
Setting range
15 - 65 °C for boilers type E
40 - 63 °C for boilers type K
00 - 01
1 - 20
30 - 100
-10 - 10
0 - 1
1 - 30
40 - 90
0 - 30
0 - 5
0 - 9
1 - 15
Parameter mode
e.g. gradient
Factory setting
60 °C
60 °C
0 0