Contractor Level - Wolf AWT Installation And Operation Instructions Manual

Weather-compensated analog control thermostat with day program for gas fired boilers
Table of Contents

Advertisement

Contractor level

Contractor level
Pressing key changes the display to contractor
level. The contractor level is segregated into
display and parameter mode. Individual
displays (e.g. A:01) and parameters (e.g. P:01)
are shown in sequence after pressing .
In parameter mode you can change the values
displayed above the r.h. rotary selector.
List of displays and parameters
Display list:
Index
Explanation
A 01
Set flow temperature
A 02
Actual flow temperature
A 03
Actual DHW temperature
Parameter list
Index
Explanation
P 01
Heating curve gradient
P 02
Room influence
P 03
Set DHW temperature
P 04
Pasteurisation
GB 01
Flow temperature hysteresis
GB 04
Upper fan speed - central heating
GB 05
Frost protection outside temperature
GB 06
Heating circuit pump mode
GB 07
Heating circuit pump run-on
GB 08
Maximum set flow temperature
GB 09
Cycle block
GB 13
Input 1
GB 14
Output 1
GB 15
DHW cylinder hysteresis
Note: Parameters GB01 to GB15 are only shown with the appropriate boilers; for descriptions see the
installation instructions of the relevant boiler.
Parameters GB 01 - 15 must only be modified by a heating contractor. Incorrect operation
Warning
can lead to system faults.
If the factory setting of parameter 5 is modified, please note that for values below 0, frost
Warning
protection is no longer ensured, consequently the heating system may suffer damage.
12
Display mode
e.g. current set
flow temperature
Unit
°C
°C
°C
Setting range
0 - 3
0 - 20
15 - 65 °C for boilers type E
40 - 63 °C for boilers type K
00 - 01
1 - 20
30 - 100
-10 - 10
0 - 1
1 - 30
40 - 90
0 - 30
0 - 5
0 - 9
1 - 15
Parameter mode
e.g. gradient
Factory setting
1.2
0
60 °C
60 °C
0 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents