FUNCTION SETTING

12-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER

Each function can be set as necessary using the remote controller. The setting of function for each unit can only be done by
the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
Function
Power failure
OFF
automatic recovery
ON
Indoor temperature
Average data from each indoor unit
Data from the indoor unit with remote controller
detecting *1
Data from main remote controller
Not supported
LOSSNAY
connectivity
Supported (Indoor unit does not intake outdoor air through LOSSNAY)
Supported (Indoor unit intakes outdoor air through LOSSNAY)
Power supply
240V
220V,230V
voltage
Frost prevention
2
(Normal)
3
temperature
When the compressor operates, the humidifier also operates.
Humidifier control
When the fan operates, the humidifier also operates.
Standard
Change of
defrosting control
For high humidity
*1 The functions above are available only when the wired remote controller is used. The functions are not available for floor
standing models.

Meaning of "Function setting"

Mode02: indoor temperature detecting
No. Indoor temperature(ta)=
No.1 Average data of the
sensor on all the
indoor units
No.2 The data of the sensor
on the indoor unit that
connected
with remote controller
No.3 The data of the sensor
on main remote
controller.
*2 Can be set only when the outdoor unit is an inverter type.
OCH415G
Settings
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
Initial
ta=(A+B)/2
setting
ta=A
ta=C
Mode No. Setting No.
01
02
03
04
15
16
17
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
ta=(A+B)/2
ta=B
ta=C
101
Initial setting
(when sent from the factory)
1
2
The setting is
1
applied to all
2
the units in the
3
same
1
refrigerant
2
system.
3
1
2
1
2
1
2
1
2
OUTDOOR
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
REMOTE
(MAIN)
(SUB)
(MAIN)
ta=A
ta=A
ta=A
ta=A
ta=C
ta=C
Remarks