Lindy Carbon Monoxide Alarm User Manual page 14

Rack monitoring system
Table of Contents

Advertisement

I
NSTALLATION AND COMMISSIONING
3
I
NSTALLATION AND COMMISSIONING
DIGITAL IN
06 12
Overload
S
Note
ALERT IN
TEMPERATURE/HUMIDITY
UPS IN
10BASET
– 8 terminal groups (of 4 terminals) for connecting 'break contact/make
contact' type devices, or devices with switching output
– Potential-free, digital
– Left terminal pair "IN+" AND "IN-" digital input
– For the connection of a break contact/make contact, an auxiliary vol-
IN+
+12V
tage of +12 V (top terminal) and an earth reference GND (bottom ter-
minal) can be connected from the right terminal pair using the enclosed
IN
GND
cable links (see connection examples below).
– U IN +5 V...+25 V
– I IN maximum 5 mA
– With auxiliary +12 V supply, maximum current draw of 200 mA
– Auxiliary voltage interruption in connection with overload or short cir-
cuit in the sensor cable:
Enter
"Fault" LED lights up.
Confirm the "overload" message in the LCD display using the ENTER key,
then switch back on in the menu "Aux.Volt." with the ENTER key (> 6 ).
In the event of interruption of auxiliary voltage, all auxiliary voltages
(and thus all sensors) are switched off!
{
– 4 terminal pairs for the connection of 4 differential signal lines or
break contact/make contact type devices (only connect passive
RMS
components)
LITE
– Maximum drawable alarm current approximately 20 mA
– For differential signal lines, ensure that the closed-circuit current of
the entire signal line does not exceed a total of 900 µA.
– 4 RJ11 modular jacks for the connection only of the Infratecplus sen-
sors available in the delivery programme (temperature sensor, humidity
sensor or combined temperature/humidity sensor)
– digital
{
– 2 terminal pairs for the connection of UPS switching outputs
– Potential-free, digital
RMS
– U IN +5 V...+25 V
LITE
– I IN maximum 5 mA
– RJ45 modular jack for connection to a 10 Mbit Ethernet
Rack

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rms liteRms advanced

Table of Contents