9-2. COOL (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION
SELECT button.
(3) Press the TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select
the desired temperature.
The setting range is 16 ~ 31°C.
w Indoor fan continues to operate regardless
of thermostat's OFF-ON at set speed.
w Coil frost prevention is as same as COOL
mode of "I FEEL CONTROL".
9-3. DRY (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room temper-
ature and determines the set temperature.
Set temperature is as shown on the right
chart.
Thermostat (SET TEMP.) does not work.
The other operations are same as DRY
mode of "I FEEL CONTROL".
(4) DRY operation will not function when the room temperature is 13°C or below.
9-4.FAN( d )OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with the OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit does not operate.
9-5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to
feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency
(High,Med.,Low), the microprocessor controls IC141 and adjusts fan motor electric current to make the current
rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the
rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot
detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut
off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION
INDICATOR lamp flashes on and off to show the fan motor abnormality. (Refer to page 30.)
9-6. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing the VANE CONTROL button.
High
AUTO
Horizontal
High
Med.
Low
Middle
Downward
23
Swing