WELDER OPERATION
WELDER OUTPUT
• Maximum Open Circuit Voltage at 3700 RPM is
80 Volts RMS.
• Duty Cycle is the percentage of time the load is
being applied in a 10 minute period. For example, a
60% duty cycle represents 6 minutes of load and 4
minutes of no load in a 10 minute period. Duty
Cycle for the RANGER® 225 GXT is 100%.
RANGER® 225 GXT
Constant Current
225 Amps AC @ 25 Volts
210 Amps DC @ 25 Volts
Constant Voltage
200 Amps DC @ 20 Volts
AUXILIARY POWER
The RANGER® 225 GXT can provide up to 9,000
watts of 120/240 volts AC, single phase 60Hz power
for continuous use, and up to 10,500 watts of 120/240
volts AC, single phase 60Hz power peak use. The
front of the machine includes three receptacles for
connecting the AC power plugs; one 50 amp 120/240
volt NEMA 14-50R receptacle and two 20 amp 120
volt NEMA 5-20R receptacles. Output voltage is within
+/-10% at all loads up to rated capacity.
All auxiliary power is protected by circuit breakers. the
120V has 20 Amp circuit breakers for each duplex
receptacle. The 120/240V Single Phase has a 40 Amp
2-pole Circuit Breaker that disconnects both hot leads
simultaneously.
CAUTION
Do not connect any plugs that connect to the
power receptacles in parallel.
------------------------------------------------------------------------
Start the engine and set the "IDLER" control switch to
the desired operating mode. Set the "CONTROL" to
10. Voltage is now correct at the receptacles for auxil-
iary power.
RANGER® 225 GXT Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current
Voltage
(Amps)
Volts
15
120
20
120
15
240
20
240
38
240
INSTALLATION
Load
Maximum Allowable Cord Length in ft. (m) for Conductor Size
(Watts)
12 AWG
14 AWG
1800
30
(9)
40 (19)
2400
30
3600
60
(18)
75 (23)
4800
60 (18)
9000
Conductor size is based on maximum 2.0% voltage drop.
RANGER® 225 GXT
120/240 VOLT DUAL VOLTAGE RECEPTACLE
The 120/240 volt receptacle can supply up to 38
amps of 240 volt power to a two wire circuit, up to 38
amps of 120 volts power from each side of a three
wire circuit (up to 76 amps total). Do not connect the
120 volt circuits in parallel. Current sensing for the
automatic idle feature is only in one leg of the three
wire circuit as shown in the following column.
*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)
120 V DUPLEX RECEPTACLES
The 120V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle.
MOTOR STARTING
Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to the machine, since the full load current rating of a
1.5 hp motor is approximately 20 amperes (10
amperes for 240 volt motors). The motor may be run
at full load when plugged into only one side of the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 240V operation
only.
10 AWG
8 AWG
75
(23)
125 (38)
(9)
50
(15)
88
(27)
150 (46)
225 (69)
100 (30)
175 (53)
50
(15)
90
(27)
GND
120 V
240 V
120 V*
6 AWG
4 AWG
175 (53)
300
(91)
138 (42)
225
(69)
350 (107)
600 (183)
275 (84)
450 (137)
150
(46)
225 (69)
A-6